2016-11-04 12:53:463RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080974
 11/4/16
  
 1) REFER TO SECTION 508.1.1: IF CHOOSING NOT TO PROVIDE
 CONDITIONED MAKEUP AIR, PLEASE PROVIDE AN AC
 CALCULATION THAT INCORPORATES THE ADDITIONAL HEAT LOAD
 FROM THE MAKEUP AIR. THE CALCULATION MUST INDICATE THAT
 THE EXISTING SYSTEM CAN HANDLE THE ADDITINAL LOAD.
 PLEASE SEE SECTION R302.1 FBC-14 ENERGY CONSERVATION
 FOR INTERIOR DESIGN TEMPERATURE (75 DEGREES F FOR
 COOLING).
  
 2) PROVIDE THE TYPES AND SIZES OF MAKEUP AIR DUCTS, AND
 REFER TO SECTION 507.9 FOR CLEARANCES TO COMBUSTIBLES.
  
 3) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE
 THE PROJECT ADDRESS ON THE PLANS.
  