Plan Review Notes For Permit 16080974 |
Permit Number |
16080974 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-11-04 12:53:46 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16080974 | | 11/4/16 | | | | 1) REFER TO SECTION 508.1.1: IF CHOOSING NOT TO PROVIDE | | CONDITIONED MAKEUP AIR, PLEASE PROVIDE AN AC | | CALCULATION THAT INCORPORATES THE ADDITIONAL HEAT LOAD | | FROM THE MAKEUP AIR. THE CALCULATION MUST INDICATE THAT | | THE EXISTING SYSTEM CAN HANDLE THE ADDITINAL LOAD. | | PLEASE SEE SECTION R302.1 FBC-14 ENERGY CONSERVATION | | FOR INTERIOR DESIGN TEMPERATURE (75 DEGREES F FOR | | COOLING). | | | | 2) PROVIDE THE TYPES AND SIZES OF MAKEUP AIR DUCTS, AND | | REFER TO SECTION 507.9 FOR CLEARANCES TO COMBUSTIBLES. | | | | 3) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE | | THE PROJECT ADDRESS ON THE PLANS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|