2016-11-04 07:20:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080972
 ADD: 2001 S. DIXIE HWY.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 04/2016
 ACTION: DENIED
  
 1) SHEET A101 THE FIRST FLOOR THE AREA OF WORK IS
 ILLUSTRATED WITH A CIRCLE AROUND THE 3 OPENINGS THAT
 ARE TO BE ALTERED FROM WINDOWS TO OVERHEAD DOOR
 CONCEPT. PLEASE NOTE THE ARCHITECTURAL PLANS WILL NEED
 TO BE UPDATED TO SHOW THE NEW OPENINGS AS OVERHEAD DOOR
 OPENINGS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (1) FLOOR PLAN
 (8) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS
  
  
 2) THE ENGINEER OF RECORD FOR THE NEW OVERHEAD DOOR
 OPENINGS WILL NEED THE ARCHITECT OF RECORD TO REVIEW
 THE PACKAGE AND APPLY THEIR SHOP DRAWING SEAL OF
 APPROVAL ON THE DOCUMENTS.
  
 3) 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
  
 4) DOCUMENTS SUBMITTED FOR A LOCAL APPROVAL FOR A
 GLAZED OVERHEAD DOOR(3) ARE MISSING DOCUMENTS FOR A
 COMPLETE CODE COMPLIANT PACKAGE.
  
 4A) THE OVERHEAD DOOR PACKAGE ADDRESSES THE FRAMEWORK,
 HYDRAULICS AND ELECTRICAL BUT DOES NOT ADDRESS THE
 REQUIREMENTS FOR 2014 FBC-B SECTION 2405 SLOPED GLAZING
 AND SKYLIGHTS
 2405.1 SCOPE.
 THIS SECTION APPLIES TO THE INSTALLATION OF GLASS AND
 OTHER TRANSPARENT, TRANSLUCENT OR OPAQUE GLAZING
 MATERIAL INSTALLED AT A SLOPE MORE THAN 15 DEGREES
 (0.26 RAD) FROM THE VERTICAL PLANE, INCLUDING GLAZING
 MATERIALS IN SKYLIGHTS, ROOFS AND SLOPED WALLS.
  
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS. SEE 2405.2 (1-2).
  
 4B) THE OVERHEAD DOOR PACKAGE ADDRESSES THE FRAMEWORK,
 HYDRAULICS AND ELECTRICAL BUT DOES NOT ADDRESS THE
 REQUIREMENTS FOR 2014 FBC-B 1710.5.1.1 EXCEPTION (2) 2.
 DOOR ASSEMBLIES INSTALLED WHERE THE OVERHANG (OH) RATIO
 IS EQUAL TO OR MORE THAN 1 NEED NOT BE TESTED FOR WATER
 INFILTRATION. THE OVERHANG RATIO SHALL BE CALCULATED BY
 THE FOLLOWING EQUATION:
  
 OH RATIO = OH LENGTH/OH HEIGHT
  
 WHERE:
  
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
  
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 4C) THE OVERHEAD DOOR PACKAGE ADDRESSES THE FRAMEWORK,
 HYDRAULICS AND ELECTRICAL BUT DOES NOT ADDRESS THE
 REQUIREMENTS FOR 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS. IN WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS
 IN BUILDINGS SHALL BE IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT-RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ANSI/DASMA 115 (FOR GARAGE
 DOORS AND ROLLING DOORS) OR TAS 201, 202 AND 203, AAMA
 506. ASTM E 1996 AND ASTM E 1886 REFERENCED HEREIN, OR
 AN APPROVED IMPACT-RESISTANT STANDARD AS FOLLOWS: (1.)
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9144 MM) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST OF ASTM E 1996.
  
 5) POWERLIFT- SCHOOL PROJECT BY DAVID RICE P. E. IS A
 DIGITALLY SIGNED PAPER COPY. NEEDS AND ORIGINAL SEAL
 AND SIGNATURE, YOU CAN NOT PRINT OUT A DIGITALLY SIGNED
 SIGNATURE FOR SUBMISSION TO THE BUILDING DEPARTMENT.
 NOTE THIS DOCUMENT COULD HAVE BEEN SUBMITTED
 ELECTRONICALLY WHERE WE COULD HAVE VALIDATED THE
 SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 6) LOCAL PRODUCT APPROVAL TO BE REVIEWED BY ROBERT
 BROWN B. O. ONCE THE PACKAGE IS COMPLETE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  