Plan Review Notes For Permit 16080942 |
Permit Number |
16080942 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-07 09:57:55 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16080942 | | 9/7/16 | | | | 1) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | SYSTEMS OF THE NEW HP-1 EM-072, AND THE RELOCATED | | EM-072- SECTION 606.2.1. | | | | 2) VERIFY MINIMUM 10' CLEARANCE FOR THE O/A INTAKES TO | | THE DRIVE OR ROADWAYS- SECTION 401.4. | | | | 3) CLARIFYHPOW AIR IS BEING RETURNED TO THE EM-048 HEAT | | PUMP UNIT. | | | | 4) PLACE TAGS AT THE RETURN AIR GRILLS. | | | | 5) PROVIDE THE FLEX DUCT SIZES ON THE MECHANICAL PLAN, | | OR RELOCATE THE SCHEDULE FROM M6.1 TO M2.1. | | | | 6) PROVIDE A WATER PIPING LAYOUT PLAN SHOWING NEW AND | | EXISTING PIPINGS, POINTS OF CONNECTIONS, LOCATIONS AND | | TYPES OF CONTROL VALVES, AND PIPE SIZES AND | | SPECIFICATIONS. | | | | 7) PROVIDE A CONDENSATE DISPOSAL PLAN. | | | | 7) SUBMIT SPECS AND/OR AN NOA FOR THE GREENHECK WALL | | CAP. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|