2016-08-30 17:01:16 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| DESCRIPTION: RENO OF EXISTING SPACE TO INCLUDE MEP, |
| FIRE ALARM & FIRE SPRINKLERS. |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. CORRECT LIGHTING FIXTURE SCHEDULE DESCRIPTION FOR F1 |
| FIXTURE. |
| 2. CORRECT ELECTRICAL SPECIFICATIONS PART 1 NOTE C TO |
| READ THE 2011 EDITION OF THE NEC. |
| 3. CORRECT ELECTRICAL SPECIFICATIONS PART 2 NOTE D. TO |
| REMOVE SCH 40 LIMITATION AS THERE ARE CONDITIONS WHICH |
| CALL FOR SCH 80. |
| 4. CORRECT ELECTRICAL SPECIFICATIONS PART 3 NOTE C TO |
| READ THE 2011 EDITION OF THE NEC. |
| 5. PER FBC-EC405.2.1.1 EACH INDIVIDUAL AREA SHALL HAVE |
| INDEPENDENT MANUAL OVERRIDE AND/OR OCCUPANCY SENSOR. |
| AREAS 104, 103, 101, 106A, 117, 112, 107, 116 ARE |
| LACKING THIS. |
| 6. PER FBC-EC405.2.2.3 DAYLIGHT ZONES SHALL BE |
| ESTABLISHED AND LIGHTING CONTROLLED INDEPENDENTLY OF |
| GENERAL AREA LIGHTING. CORRECT LIGHTING LAYOUT |
| ACCORDINGLY. |
| 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT |
| SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. THIS |
| PENDANT LIGHT MAY NOT BE AUTOMATICALLY CONTROLLED AND |
| SHALL BE SUFFICIENT TO PROVIDE AMPLE LIGHTING TO WORK |
| INSIDE THE ELECTRICAL PANELS. |
| 8. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15- |
| AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| 90.1) |
| 9. FIRE ALARM WORK SHALL BE COMPLETED UNDER SEPARATE |
| PERMIT AND SUBMITTAL. |
| 10. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, |
| 15- AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| 90.1) |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |