2016-08-30 17:01:16ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 DESCRIPTION: RENO OF EXISTING SPACE TO INCLUDE MEP,
 FIRE ALARM & FIRE SPRINKLERS.
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. CORRECT LIGHTING FIXTURE SCHEDULE DESCRIPTION FOR F1
 FIXTURE.
 2. CORRECT ELECTRICAL SPECIFICATIONS PART 1 NOTE C TO
 READ THE 2011 EDITION OF THE NEC.
 3. CORRECT ELECTRICAL SPECIFICATIONS PART 2 NOTE D. TO
 REMOVE SCH 40 LIMITATION AS THERE ARE CONDITIONS WHICH
 CALL FOR SCH 80.
 4. CORRECT ELECTRICAL SPECIFICATIONS PART 3 NOTE C TO
 READ THE 2011 EDITION OF THE NEC.
 5. PER FBC-EC405.2.1.1 EACH INDIVIDUAL AREA SHALL HAVE
 INDEPENDENT MANUAL OVERRIDE AND/OR OCCUPANCY SENSOR.
 AREAS 104, 103, 101, 106A, 117, 112, 107, 116 ARE
 LACKING THIS.
 6. PER FBC-EC405.2.2.3 DAYLIGHT ZONES SHALL BE
 ESTABLISHED AND LIGHTING CONTROLLED INDEPENDENTLY OF
 GENERAL AREA LIGHTING. CORRECT LIGHTING LAYOUT
 ACCORDINGLY.
 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. THIS
 PENDANT LIGHT MAY NOT BE AUTOMATICALLY CONTROLLED AND
 SHALL BE SUFFICIENT TO PROVIDE AMPLE LIGHTING TO WORK
 INSIDE THE ELECTRICAL PANELS.
 8. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 9. FIRE ALARM WORK SHALL BE COMPLETED UNDER SEPARATE
 PERMIT AND SUBMITTAL.
 10. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT,
 15- AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER