Date |
Text |
2016-08-24 08:32:33 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16080940 |
| W. P. B. PERMIT: 16010466 |
| ADD: 2400 N FLAGLER DR. CURY PARK/ CITY PUMP/ LIFT |
| STATION ADDITION & RENOVATION/ ANTENNA TOWER & BASE |
| BLDG. RISK CATEGORY: IV/ 180 VULT/ MPH |
| CONT: FLORIDA DESIGN DRILLING CORP. |
| TEL: 561-844-2966 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. AUG. 24/ 2016 |
| ACTION: DENIED |
| |
| 1) THIS STRUCTURE IS IN AN A5 FLOOD ZONE, FBC BUILDING |
| 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE WILL BE REQUIRED. |
| |
| PLEASE NOTE THE TOP OF THE BASE IS IN NGVD AND THE |
| GROUND LEVEL NEXT TO THE BASE. THE OTHER CRITICAL |
| INFORMATION THAT WILL NEED TO BE FILED OUT ON THE FLOOD |
| ZONE CERTIFICATE IS WHAT ELEVATION (IN NGVD) THE |
| ELECTRICAL EQUIPMENT ASSOCIATED WITH THE ANTENNA IS |
| LOCATED. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31/2015 |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |