Plan Review Notes
Plan Review Notes For Permit 16080928
Permit Number 16080928
Review Stop M
Sequence Number 4
Notes
Date Text
2017-03-27 10:37:57RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME OR IF RE-SUBMITTING CORRECT INFORMATION.
  
 1- REVISED EQUIPMENT CALCULATIONS FOR THE REAR
 STRUCTURE NEEDS TO BE REVISED. SELECTED EQUIPMENT NEEDS
 TO BE CHANGED. "THE CORRESPONDING LATENT CAPACITY OF
 THE EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED
 LATENT LOAD". SEC. R403.6.1.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 2- EQUIPMENT SHOWN ON DRAWING M1 FOR THE REAR STRUCTURE
 DOESN'T MATCH EQUIPMENT SHOWN ON THE REVISED EQUIPMENT
 SIZING CALCULATIONS. REVISE AS REQUIRED TO MATCH ,
 INCLUDING THE SEER. SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION.
  
 3- ONLY THE SUMMARY SHEET OF THE EQUIPMENT SIZING
 CALCULATIONS WAS SUBMITTED. PROVIDE THE COMPLETE
 EQUIPMENT SIZING CALCULATIONS FOR THE MAIN HOUSE AND
 FOR THE REAR STRUCTURE. SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  