Plan Review Notes For Permit 16080928 |
Permit Number |
16080928 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2017-03-27 10:37:07 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION BUILDING | | REVIEW CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | NOTE: | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION | | AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO | | AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY. | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | THIS TIME OR IF RE-SUBMITTING CORRECT INFORMATION. | | | | 1- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE | | CONVERSION: THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF | | 4 DOESN'T MATCH PLANS. THERE ARE NO WINDOWS ON THE | | NORTH SIDE AND OVERHANG SEPARATION IS INCORRECT. REVISE | | AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2 | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|