2017-02-06 11:16:34RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD
 MECHANICAL REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL
 NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI
 LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH
 EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED.
 NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH
 SEPARATE STRUCTURE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
 NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING
 CALCULATIONS FOR EACH BUILDING. ONLY A ONE SUMMARY FOR
 THE MAIN HOUSE WAS SUBMITTED. PROVIDE COMPLETE LOAD
 CALCULATIONS FOR EACH BUILDING.
  
 2- PROVIDE MANUFACTURER'S INFORMATION FOR THE A/C UNIT
 SPECIFIED FOR THE GARAGE CONVERSION SHOWING THE SEER
 SPECIFIED ON PLANS. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  