Plan Review Notes
Plan Review Notes For Permit 16080928
Permit Number 16080928
Review Stop B
Sequence Number 3
Notes
Date Text
2017-02-03 18:36:26RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- MISSING PLANS WITH THE PALM BEACH COUNTY STAMP FOR
 IMPACT FEES. PLEASE BRING COPY OF PLANS THAT WERE
 STAMPED BY PALM BEACH COUNTY. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE
 CONVERSION:
 A) OWNER NEEDS TO CERTIFY AT BOTTOM OF FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY
 CALCULATIONS.
  
 B) ITEM #5 INDICATES THAT CALCULATIONS ARE NOT DONE FOR
 WORST CASE SCENARIO BUT PAGE 2 OF 4 INDICATES THAT THE
 BUILDING WAS ROTATED 45 DEGREES. ENERGY CALCULATIONS
 NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE
 BUILDING. THEY CAN NOT BE ROTATED. REVISE AS REQUIRED.
 SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE; REPEAT COMMENT. NOT ADDRESSED.
  
 C) THE GARAGE FLOOR IS NOT A RAISED FLOOR. SEE PLANS
 AND REVISE ITEM #8 AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) REVISE WALL INFORMATION ON ITEM #9. ACCORDING TO
 PLANS THE EXISTING STRUCTURE IS CONCRETE BLOCK
 CONSTRUCTION NOT WOOD FRAMED CONSTRUCTION. AND, THE
 OPENINGS LIKE THE EXISTING GARAGE DOOR OPENING IS
 CLOSED WITH WOOD FRAMED CONSTRUCTION. REVISE AS
 REQUIRED. PROVIDE INFORMATION FOR THE TWO TYPES OF
 WALLS TO MATCH PLANS. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE "SPACES" IN FORMATION ON PAGE 2 OF 4. UNIT
 CAN NOT HAVE A KITCHEN. SEE ZONING COMMENTS AND REVISED
 PLANS. REVISE AS REQUIRED. REMOVE THE KITCHEN. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE THE BUILDING ORIENTATION, TOTAL
 SQUARE FOOTAGE AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 G) BUILDER NEEDS TO COMPLETE THE EPL DISPLAY CARD. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE; REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE A/C MANUFACTURER'S SPECS FOR 18 SEER A/C
 UNIT AS SPECIFIED ON THE ENERGY CALCULATIONS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]