2016-11-16 10:26:25 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND |
| MECHANICAL REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY |
| SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL |
| NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI |
| LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH |
| EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED. |
| CHECK CFM'S SPECIFIED FOR UNIT #1 AND UNIT #2. WHY THE |
| GUEST HOUSE HAS MORE CFM'S THAN THE MAIN HOUSE? |
| NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH |
| SEPARATE STRUCTURE. |
| |
| RESPONSE: |
| NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING |
| CALCULATIONS FOR EACH BUILDING. ONLY A ONE SUMMARY FOR |
| THE MAIN HOUSE WAS SUBMITTED. PROVIDE COMPLETE LOAD |
| CALCULATIONS FOR EACH BUILDING. |
| |
| NEW COMMENT: |
| 2- PROVIDE MANUFACTURER'S INFORMATION FOR THE A/C UNIT |
| SPECIFIED FOR THE GARAGE CONVERSION SHOWING THE SEER |
| SPECIFIED ON PLANS. SEC. R103.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |