Plan Review Notes For Permit 16080928 |
Permit Number |
16080928 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-11-01 12:08:40 | 2ND ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PRIOR COMMENTS ADDRESSED. BASED ON NEW SERVICE | | ARRANGEMENT SHOWN, THE MAIN BREAKERS MUST BE GROUPED IN | | ONE LOCATION PER FBC RES E3601.7 AND THE SHOW A | | GROUNDING ELECTRODE ARRANGEMENT AT THE SEPARATE | | STRUCTURE. SEPARATE STRUCTURE MUST STILL BE MCB PANEL | | TYPE NOT A MLO. | | 2. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|