2016-09-19 15:17:18 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL |
| REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY |
| SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL |
| NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI |
| LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH |
| EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED. |
| CHECK CFM'S SPECIFIED FOR UNIT #1 AND UNIT #2. WHY THE |
| GUEST HOUSE HAS MORE CFM'S THAN THE MAIN HOUSE? |
| NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH |
| SEPARATE STRUCTURE. |
| |
| 2- BALANCE RETURN INFORMATION FOR BEDROOM #2 IS NOT |
| CLEAR. CLEARLY SPECIFY SIZE OF TRANSFER DUCT FOR |
| BEDROOM #2. SEE SIZE OF GRILLE SPECIFIED. AND, PROVIDE |
| DETAILS SHOWING HOW IS IT GOING TO BE INSTALLED WITHOUT |
| INTERFERING WITH THE AIR HANDLER UNIT ABOVE. SEC. |
| M1602.4 FBC-RESIDENTIAL. 5TH EDITION (2014). |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |