Plan Review Notes For Permit 16080872 |
Permit Number |
16080872 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-08-27 08:45:53 | 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION | | NOTES THAT THIS TRAILER IS A CONSTRUCTION TRAILER WHEN | | IN FACT IT IS BEING UTILIZED FOR PROMOTING CARP AND WAS | | OPEN TO THE PUBLIC. REVISE THE DESCRIPTION OF WORK ON | | THE APPLICATION TO REFLECT THE ACTUAL USE OF THE | | TRAILER. WPB AMEND. TO FBC SEC.107.2.1. | | 2) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE | | TRAILER ON THE SITE ALONG WITH THE LOCATION OF THE | | WATER SERVICE AND THE SANITARY HOLDING TANK.WPB AMEND. | | TO FBC SEC. 107.3.5.1. | | 3) THE PLANS SHALL BE DRAWN UPON SUITABLE MATERIAL PER | | WPB AMEND. TO FBC SEC.107.2.1. | | 4) THE WATER SERVICE TO THE TRAILER SHALL BE EQUIPPED | | WITH A BACKFLOW PREVENTION DEVICE TO PREVENT | | CONTAMINATION FROM NONPOTABLE SOURCES IN ACCORDANCE | | WITH 2014 FPC SEC.608.1. | | 5) THE SIZE OF THE WATER SERVICE TO THE TRAILER SHALL | | COMPLY WITH 2014 FPC SEC. 603.1. | | 6) SUBMIT A COPY OF THE PUMP OUT AGREEMENT FOR THE | | SANITARY HOLDING TANK. FPC 311.1. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|