Plan Review Notes
Plan Review Notes For Permit 16080855
Permit Number 16080855
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-23 08:12:55RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- ACCORDING TO SEC. 489.113(3)(G) FLORIDA STATUTES A
 GENERAL CONTRACTOR WHO IS LICENSED AFTER 1973 CAN NOT
 DO ROOFING WORK UNLESS HE/SHE IS LICENSED AS A ROOFING
 CONTRACTOR. ACCORDING TO DBPR THIS CONTRACTOR WAS
 LICENSED ON JUNE 30, 1989. THEREFORE, CAN NOT DO THE
 ROOFING WORK. NEED ROOFING CONTRACTOR TO APPLY FOR THE
 JOB.
  
 2- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS (2 COPIES WITH ORIGINAL SEAL AND
 SIGNATURE) AS REQUIRED BY GENERAL LIMITATION #7 OF NOA
 14-1030.02 SUBMITTED. NEED THE CALCULATIONS TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. 1609.1 FBC-BUILDING,
 5TH EDITION (2014).
  
 3- ROOF TILE: PROVIDE CALCULATIONS SHOWING THE ROOF
 TILE MOMENT OF RESISTANCE OR ALL ROOF ZONES TO VERIFY
 THAT 1 SCREW IS ADEQUATE TO RESIST THE WIND LOADS. SEC.
 1609.1 FBC-BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712