2016-08-20 06:23:58 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16080782 |
| ADD: 1301 SUMMIT BLVD. (WHITE ALLIGATOR BUILDING) |
| CONT: ROOFING UNLIMITED |
| TEL: 561-842-0025 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. AUGUST 20/2016 |
| ACTION: DENIED |
| |
| 1) ONLY ONE SET OF ROOFING PRODUCT APPROVALS WERE |
| SUBMITTED. ) INFORMATIONAL 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1.3: PLEASE SUBMIT 2 OF ALL |
| SURVEYS, PLANS, REPORTS, REVISIONS, PRODUCT APPROVALS |
| AND OR SUBMITTALS FOR REVIEW FOR PERMIT. |
| |
| 2) THE SUBMITTED PRODUCT APPROVALS HAVE NOT BEEN |
| REVIEWED BY THE DESIGNER OF RECORD. ADMINISTRATION |
| 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING |
| SUBMITTAL DOCUMENTS PREPARED BY OTHERS, INCLUDING |
| PHASED AND DEFERRED SUBMITTAL ITEMS, FOR COMPATIBILITY |
| WITH THE DESIGN OF THE BUILDING. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 3) PLEASE NOTE THE DESIGNER OF RECORD THOMAS L. ADAMS |
| P. E. LIST PRESSURES ON SHEET S0.1 FOR COMPONENTS AND |
| CLADDING IN VULT AND VASD FOR ROOF ZONES 1-3. ROOF ZONE |
| 3 IS LISTED AT A -89.1. THE SUBMITTED APPROVAL FL |
| 14645-R2 METAL SALES MANUFACTURING CORP., 14645.1 2.5 |
| CORRUGATED ROOFING IS ONLY GOOD FOR -86.0. SEE PAGE 2 |
| OF 3 IN THE REPORT. PLEASE ALSO SEE PRODUCT LIMITATION. |
| THE MAXIMUM FASTENER SPACING LISTED HEREIN SHALL NOT BE |
| EXCEEDED. |
| |
| 4) THE CONTRACTOR DID NOT INDICATE WHICH SUB-SYSTEM OF |
| THE POLYGLASS FL 5259-R24 WAS TO BE INSTALLED SEE |
| ASSOCIATED PRESSURES FOR SUB-SYSTEMS. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |