2016-08-20 06:23:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080782
 ADD: 1301 SUMMIT BLVD. (WHITE ALLIGATOR BUILDING)
 CONT: ROOFING UNLIMITED
 TEL: 561-842-0025
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. AUGUST 20/2016
 ACTION: DENIED
  
 1) ONLY ONE SET OF ROOFING PRODUCT APPROVALS WERE
 SUBMITTED. ) INFORMATIONAL 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3: PLEASE SUBMIT 2 OF ALL
 SURVEYS, PLANS, REPORTS, REVISIONS, PRODUCT APPROVALS
 AND OR SUBMITTALS FOR REVIEW FOR PERMIT.
  
 2) THE SUBMITTED PRODUCT APPROVALS HAVE NOT BEEN
 REVIEWED BY THE DESIGNER OF RECORD. ADMINISTRATION
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING
 SUBMITTAL DOCUMENTS PREPARED BY OTHERS, INCLUDING
 PHASED AND DEFERRED SUBMITTAL ITEMS, FOR COMPATIBILITY
 WITH THE DESIGN OF THE BUILDING. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) PLEASE NOTE THE DESIGNER OF RECORD THOMAS L. ADAMS
 P. E. LIST PRESSURES ON SHEET S0.1 FOR COMPONENTS AND
 CLADDING IN VULT AND VASD FOR ROOF ZONES 1-3. ROOF ZONE
 3 IS LISTED AT A -89.1. THE SUBMITTED APPROVAL FL
 14645-R2 METAL SALES MANUFACTURING CORP., 14645.1 2.5
 CORRUGATED ROOFING IS ONLY GOOD FOR -86.0. SEE PAGE 2
 OF 3 IN THE REPORT. PLEASE ALSO SEE PRODUCT LIMITATION.
 THE MAXIMUM FASTENER SPACING LISTED HEREIN SHALL NOT BE
 EXCEEDED.
  
 4) THE CONTRACTOR DID NOT INDICATE WHICH SUB-SYSTEM OF
 THE POLYGLASS FL 5259-R24 WAS TO BE INSTALLED SEE
 ASSOCIATED PRESSURES FOR SUB-SYSTEMS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION