Plan Review Notes For Permit 16080691 |
Permit Number |
16080691 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-18 11:38:17 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. TWO SETS OF THE ROOF PLAN WERE SUBMITTED. THREE | | COMPLETE SETS REQUIRED, FBC 107. | | | | 2. TWO SETS OF THE ROOF TILE PRODUCT APPROVAL AND | | ENGINEERING WERE SUBMITTED; THREE REQUIRED, FBC 107. | | | | 3. THE ENGINEERING FOR THE ROOF TILE ATTACHMENT IS A | | PHOTOCOPY. FS471, DOCUMENTS PREPARED BY AN ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED | | DATED ORIGINALS. | | | | 4. SEE PRIOR CORRECTION LISTS. IF A REVIEW LETTER IS | | SUBMITTED IN LIEU OF AN INTIALED/DATED SHOP DRAWING | | REVIEW STAMP DIRECTLY ON THE SUBMITTAL, THE LETTER IS | | TO BE SIGNED AND SEALED (PER BUILDING OFFICIAL), FBC | | 107. | | | | 5. PRODUCT APPROVALS ARE TO BE REVIEWED BY THE DESIGNER | | OF RECORD PRIOR TO SUBMITTAL, FBC 107 (ROOF HATCH | | PRODUCT APPROVAL). | | | | 6. THE ROOF HATCH PRODUCT APPROVAL IS ILLEGIBLE DUE TO | | THE SIZE. THE DRAWING SHEETS WERE PRINTED HALF SIZE | | (PORTRAIT ORIENTATION RATHER THAN LANDSCAPE). THIS | | DOCUMENT IS USED FOR PLAN REVIEW, INSPECTIONS, AND | | RETAINED AS A PART OF THE PERMIT RECORD FOREVER. A | | CLEAR LEGIBLE COPY IS REQUIRED, FBC 107. | | | | 7. THE BASE SHEET CALCULATIONS ARE A PHOTOCOPY. | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED DATED ORIGINALS, | | FS471. | | |
|