Plan Review Notes For Permit 16080682 |
Permit Number |
16080682 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-17 09:17:15 | 2130 CENTREPARK DRIVE WEST - 1ST FLOOR | | PERMIT #16080682 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PLAN IS REQUIRED TO BE SIGNED/SEALED BY A PROFESSIONAL | | ENGINEER WHEN THE SCOPE OF WORK EXCEEDS 49 SPRINKLERS. | | THE WORK SCOPE IS 101 (30 & 71) SPRINKLERS BETWEEN THE | | TWO PERMITS (#16080682 AND #16080683). | | | | SUBMIT HYDRAULIC CALCULATIONS SUPPORTING THE USE OF THE | | FLEXIBLE SPRINKLER CONNECTIONS. | | | | SUBMIT PRODUCT CUTSHEETS FOR FLEXIBLE CONNECTIONS. | | | | PLANS DO NOT INDICATE THE CEILING OR SOFFIT HEIGHTS. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | | | |
|