2016-08-17 09:17:152130 CENTREPARK DRIVE WEST - 1ST FLOOR
 PERMIT #16080682
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN IS REQUIRED TO BE SIGNED/SEALED BY A PROFESSIONAL
 ENGINEER WHEN THE SCOPE OF WORK EXCEEDS 49 SPRINKLERS.
 THE WORK SCOPE IS 101 (30 & 71) SPRINKLERS BETWEEN THE
 TWO PERMITS (#16080682 AND #16080683).
  
 SUBMIT HYDRAULIC CALCULATIONS SUPPORTING THE USE OF THE
 FLEXIBLE SPRINKLER CONNECTIONS.
  
 SUBMIT PRODUCT CUTSHEETS FOR FLEXIBLE CONNECTIONS.
  
 PLANS DO NOT INDICATE THE CEILING OR SOFFIT HEIGHTS.
  