2016-08-16 18:50:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE SLOPE OF THE FLAT ROOF (MINIMUM 1/4" PER
 FOOT) AND THE MEAN ROOF HEIGHT OF THE STRUCTURE. FBC
 107.2.1 AND FBC R 905.15.1
  
 2) THE ROOFING SYSTEM THAT YOU SELECTED ON PAGE 12 OF
 NOA 13-0204.17 HAS A MAXIMUM DESIGN PRESSURE OF -45
 PSF. THE STRUCTURE IS LOCATED IN EXPOSURE C WITH A VULT
 WIND SPEED OF 170 MPH. THE PERIMETER AND CORNER ROOF
 AREAS HAVE HIGHER NEGATIVE PRESSURE THAN THE DESIGN
 PRESSURE AND WILL REQUIRE ENHANCED FASTENING. SUBMIT
 TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY LIMITATION NUMBER 7 ON PAGE 14. FBC R
 905.15.3