2016-08-16 18:50:44 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE SLOPE OF THE FLAT ROOF (MINIMUM 1/4" PER | | FOOT) AND THE MEAN ROOF HEIGHT OF THE STRUCTURE. FBC | | 107.2.1 AND FBC R 905.15.1 | | | | 2) THE ROOFING SYSTEM THAT YOU SELECTED ON PAGE 12 OF | | NOA 13-0204.17 HAS A MAXIMUM DESIGN PRESSURE OF -45 | | PSF. THE STRUCTURE IS LOCATED IN EXPOSURE C WITH A VULT | | WIND SPEED OF 170 MPH. THE PERIMETER AND CORNER ROOF | | AREAS HAVE HIGHER NEGATIVE PRESSURE THAN THE DESIGN | | PRESSURE AND WILL REQUIRE ENHANCED FASTENING. SUBMIT | | TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY LIMITATION NUMBER 7 ON PAGE 14. FBC R | | 905.15.3 |
|