Plan Review Notes
Plan Review Notes For Permit 16080659
Permit Number 16080659
Review Stop M
Sequence Number 2
Notes
Date Text
2016-10-17 17:31:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080659
 10/17/16
  
 1) THE AC CALCULATIONS MUST BEAR THE SIGNATURE AND SEAL
 OF THE ENGINEER WHO PREPARED THEM- SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION, AND SECTION 61G15-23.002
 FAC.
  
 2) THE PLAN DOES NOT CLEARLY INDICATE HOW AIR WILL BE
 RETURNED TO THE RTU FROM THE TECH ROOM, THE WEST AND
 NORTH OFFICES, THE RECEPTION ROOM, THE WORK AREAS, AND
 CORRIDORS. PLEASE REFER TO SHEETS A-1.0 AND A-3.0: THE
 D WALL TYPE AND THE GLASS PARTITION AND HEADERS ARE
 SHOWN TO BE SPANNING FROM THE FLOOR TO THE STRUCTURE
 ABOVE. A) ADVISORY: PLEASE REFER TO SECTION 601.2:
 CORRIDORS SHALL NOT SERVE AS RETURN DUCTS.
  
 3) PROVIDE THE ROOF PLAN SHEET A1.1 SHOWN IN THE INDEX.
  
 4) THE ARCHITECT HAS REQUESTED THE ENGINEERING FOR
 INSTALLATION OF THE RTU, CURB ADAPTER, AND ROOF STAND
 BE DEFFERRED SUBMITTALS. PLEASE NOTE THAT THE
 ENGINEERING MUST BE SUBMITTED AND APPROVED PRIOR TO
 INSPECTION OF THE INSTALLATIONS.
  
 A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  