2016-09-07 17:02:161ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16080659
 9/7/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTUION C403.2.1 FBC-14 ENERGY
 CONSERVATION. THE SUMMARY CALCULATION ON SHEET M-1 IS
 INCOMPLETE.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV BOXES, AND
 TYPICAL BOX INSTALLATION DETAILS.
  
 3) THE RTU, CONDENSER, AND ROOFTOP FAN EQUIPMENT
 MOUNTING DETAILS ARE INCOMPLETE. PLEASE PROVIDE THE
 WIND LOAD DESIGN CRITERIA AND COMPLETE ANCHORING AND
 FASTENING DETAILS- SECTION 301.15. SUBMIT A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE ROOF STAND.
  
 4) PROVIDE A CONDENSATE DISPOSAL PLAN.
  