Date Text
2016-09-14 18:51:511ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 324 DATURA STREET
 DESCRIPTION: INTERIOR REMODEL OF 4TH FLOOR
 MASTER PERMIT: 15011034
 REVISION # 16080659
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH
 DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE
 GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS
 SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE.
 CORRECT ELECTRICAL GENERAL NOTE #7 ACCORDINGLY.
 2. INDICATE ON THE RISER DIAGRAM WHAT IS EXISTING TO
 REMAIN VS. WHAT IS NEW.
 3. FBC-E405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 4. NEC 210.63: A 125 VOLT, SINGLE-PHASE, 15 OR
 20-AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTALLED AT
 AN ACCESSIBLE LOCATION FOR THE SERVICING OF HVAC
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED WITHIN 25
 FT. OF THE EQUIPMENT. IN LIEU OF A ROOF PLAN YOU SHALL
 PROVIDE A DETAIL OF THE HVAC EQUIPMENT WITH ITS
 REQUIRED SERVICE OUTLET.
 5. FBC-EC405.2.2.3: DAYLIGHT ZONE CONTROL SHALL BE
 PROVIDED FOR THE: BREAK ROOM, TECH ROOM AND VARIOUS
 WORK AREAS.
 6. NEC 110.26(D): THE LIGHTING IN THE ELECTRIC ROOM
 CANNOT BE CONTROLLED AUTOMATICALLY.
 7. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE
 TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING
 TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION.
 PROVIDE A LIGHT DENSITY ALLOWANCE CHART TO SHOW
 COMPLIANCE.
 8. ALL FIRE ALARM WORK TO BE CONDUCTED UNDER A SEPARATE
 PERMIT AND SUBMITTAL.
  
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  