2016-09-14 18:51:51 | 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: |
| JOB ADDRESS: 324 DATURA STREET |
| DESCRIPTION: INTERIOR REMODEL OF 4TH FLOOR |
| MASTER PERMIT: 15011034 |
| REVISION # 16080659 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH |
| DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE |
| GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS |
| SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE. |
| CORRECT ELECTRICAL GENERAL NOTE #7 ACCORDINGLY. |
| 2. INDICATE ON THE RISER DIAGRAM WHAT IS EXISTING TO |
| REMAIN VS. WHAT IS NEW. |
| 3. FBC-E405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15- |
| AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| 90.1) |
| 4. NEC 210.63: A 125 VOLT, SINGLE-PHASE, 15 OR |
| 20-AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTALLED AT |
| AN ACCESSIBLE LOCATION FOR THE SERVICING OF HVAC |
| EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED WITHIN 25 |
| FT. OF THE EQUIPMENT. IN LIEU OF A ROOF PLAN YOU SHALL |
| PROVIDE A DETAIL OF THE HVAC EQUIPMENT WITH ITS |
| REQUIRED SERVICE OUTLET. |
| 5. FBC-EC405.2.2.3: DAYLIGHT ZONE CONTROL SHALL BE |
| PROVIDED FOR THE: BREAK ROOM, TECH ROOM AND VARIOUS |
| WORK AREAS. |
| 6. NEC 110.26(D): THE LIGHTING IN THE ELECTRIC ROOM |
| CANNOT BE CONTROLLED AUTOMATICALLY. |
| 7. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE |
| TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING |
| TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION. |
| PROVIDE A LIGHT DENSITY ALLOWANCE CHART TO SHOW |
| COMPLIANCE. |
| 8. ALL FIRE ALARM WORK TO BE CONDUCTED UNDER A SEPARATE |
| PERMIT AND SUBMITTAL. |
| |
| |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |