2016-09-10 08:30:45 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16080659 (NOT A REVISION) |
| ADD: 324 DATURA STREET / SUITE :400 |
| CONT: GERARD CONTRACTING |
| TEL: 561-373-3542 |
| E-MAIL: ??????????? PLEASE PROVIDE E-MAIL ADDRESS |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. SEPT.10/2016 |
| ACTION: DENIED |
| |
| 1) THIS IS NOT A REVISION TO AN INTERIOR DEMOLITION |
| PERMIT. BEFORE PERMIT ISSUANCE FILL OUT A PERMIT |
| APPLICATION FORM AND PAY THE APPROPRIATE PERMIT FEES. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 105.1 PERMIT REQUIRED. |
| |
| 2) THE COVER SHEET CS-1 LIST THIS BUILDING TYPE AS AN |
| IB/ UNPROTECTED SPRINKLERED. SEE TABLE 601 FOR A TYPE |
| IB BUILDING THE STRUCTURAL MEMBER ARE PROTECTED 2 |
| HOURS. TYPE IB/PROTECTED/ SPRINKLERED. |
| |
| 3)SHEET A-1.0 PLEASE REVIEW GLAZING IN OFFICES |
| 102,103,104, 106, 107, 108, 109, 119, 120 & 121 ALL |
| INDICATE GLASS WALLS. THERE ARE NO SECTIONS THRU A |
| GLASS WALL INDICATING SEE THIS SECTION. PLEASE PROVIDE |
| HOW CODE COMPLIANCE WILL BE ACCOMPLISHED EITHER USING |
| CPSC CFR PART 1201 OR ANSI Z97.1 2406.2 IMPACT TEST. |
| |
| 4) SHEET A-1.0 ALSO INDICATES DOOR TYPES A1 & B1 AS |
| GLASS DOORS. PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE |
| ACCOMPLISHED EITHER USING CPSC CFR PART 1201 OR ANSI |
| Z97.1 2406.2 IMPACT TEST. |
| |
| 5) SHEET A-1 SHOWS IN THE LOWER LEFT CORNER A RESTROOM |
| DETAIL WITH THE WATER CLOSET GRAB BARS MEASURED TO THE |
| CENTER LINE. UNDER THE 2014 FBC-ACCESS. CODE 609.4. |
| THE HEIGHT OF THE WATER CLOSET GRAB BAR IS MEASURED |
| FROM THE TOP OF THE GRIPPING SURFACE TO THE FINISH |
| FLOOR NOT THE MID LINE. |
| |
| 6) SHEET A-1 THE ACCESSIBLE MIRROR IN THE RESTROOM IS |
| SHOWN TO BE 40 INCHES TO THE BOTTOM OF THE MIRROR. |
| PLEASE REVIEW THE 2014 FBC-ACCESS. CODE 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 7) PLEASE PROVIDE SIGNAGE SEE 2014 FBC-ACCESS. CODE ; |
| 216.3 DIRECTIONAL AND INFORMATIONAL SIGNS. |
| 216.4 MEANS OF EGRESS. |
| 703.1. SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL |
| AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN |
| WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO |
| SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE |
| CHARACTERS, SHALL BE PROVIDED. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 9) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |