Plan Review Notes
Plan Review Notes For Permit 16080657
Permit Number 16080657
Review Stop P
Sequence Number 1
Notes
Date Text
2016-09-14 03:38:24 
 PARK PALM BEACH MULTIFAMILY RESIDENTIAL
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: 9/14/2016
 ACTION:DENIED
  
 1) SHEET A-3.10 - SINGLE BEDROOM/ BATH UNIT. THE BATH
 MUST BE A SPECIFICATION A OR SPECIFICATION B, THIS
 DESIGN IS NEITHER AN A OR B SPECIFICATION. TO HAVE THE
 VALVES AS SHOWN YOU WOULD HAVE TO HAVE A 30X 48 INCH
 PARALLEL APPROACH WITH THE 48 INCHES STARTING AT THE
 CONTROL WALL AND PARALLELING THE TUB. THE WATER CLOSET
 IS IN THE WAY. THE WATER CLOSET WOULD NEED TO BE A
 MINIMUM OF 30 INCHES AWAY FROM THE TUB TO THE EDGE OF
 THE WATER CLOSET. THE ORIGINAL DESIGN OF THE FAIR
 HOSING GUIDELINES SHOW THE CONTROL VALVES ARE ON THE
 SAME WALL AS THE WATER CLOSET. THIS CONFORMS TO THE
 SPECIFICATION A.
  
 THE DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO
 WHICH STANDARD THE UNIT BATHROOMS WERE DESIGNED.
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
  
 2A) SHEET A3.22 SHOWS A DWELLING UNIT WITH 2 BEDROOMS
 AND 2 BATHROOMS, ONE HAS A TUB THE OTHER A SHOWER. THE
 DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO WHICH
 STANDARD THE UNIT BATHROOMS WERE DESIGNED.
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
 IF THE DESIGNER INDICATES THAT BATHROOM # 2 IS DESIGNED
 AS THE SPECIFICATION B THEN THE REQUIREMENTS HAVE BEEN
 SATISFIED.
  
 2B) SHEET A3.22 DETAIL # 9 ONLY GIVE THE REQUIRED
 LOCATION FOR THE BACKING AND GRAB BAR FOR THE TOE END
 OF THE TUB. NOT THE BACK WALL NOR THE HEAD OF THE TUB.
 SEE FIGURE "4" FROM FAIR HOUSING REQS. IN 2010 FAC &
 ALSO 24 CFR 100.205.
  
 3) SHT. A-3.10 & A-.21 - WATER SUPPLY VALVES FOR THE
 STACKED WASHER/DRYER UNIT SHALL BE ACCESSIBLE PER 2010
 FPC SEC.606.3.
  
 4) SHT. A-3.41 - SHOW THE LENGTH AND WIDTH DIMENSIONS
 OF THE ACCESSIBLE TOILET ROOMS ON DETAILS #3 & #4.
  
 5)WHEN SUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  