2016-09-14 03:38:24 | |
| PARK PALM BEACH MULTIFAMILY RESIDENTIAL |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| |
| 1ST REVIEW |
| DATE: 9/14/2016 |
| ACTION:DENIED |
| |
| 1) SHEET A-3.10 - SINGLE BEDROOM/ BATH UNIT. THE BATH |
| MUST BE A SPECIFICATION A OR SPECIFICATION B, THIS |
| DESIGN IS NEITHER AN A OR B SPECIFICATION. TO HAVE THE |
| VALVES AS SHOWN YOU WOULD HAVE TO HAVE A 30X 48 INCH |
| PARALLEL APPROACH WITH THE 48 INCHES STARTING AT THE |
| CONTROL WALL AND PARALLELING THE TUB. THE WATER CLOSET |
| IS IN THE WAY. THE WATER CLOSET WOULD NEED TO BE A |
| MINIMUM OF 30 INCHES AWAY FROM THE TUB TO THE EDGE OF |
| THE WATER CLOSET. THE ORIGINAL DESIGN OF THE FAIR |
| HOSING GUIDELINES SHOW THE CONTROL VALVES ARE ON THE |
| SAME WALL AS THE WATER CLOSET. THIS CONFORMS TO THE |
| SPECIFICATION A. |
| |
| THE DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO |
| WHICH STANDARD THE UNIT BATHROOMS WERE DESIGNED. |
| IF SPECIFICATION A IS SELECTED AS THE BASIS FOR |
| DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING |
| UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF |
| SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE |
| DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER |
| BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE |
| ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING. |
| |
| 2A) SHEET A3.22 SHOWS A DWELLING UNIT WITH 2 BEDROOMS |
| AND 2 BATHROOMS, ONE HAS A TUB THE OTHER A SHOWER. THE |
| DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO WHICH |
| STANDARD THE UNIT BATHROOMS WERE DESIGNED. |
| IF SPECIFICATION A IS SELECTED AS THE BASIS FOR |
| DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING |
| UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF |
| SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE |
| DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER |
| BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE |
| ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING. |
| IF THE DESIGNER INDICATES THAT BATHROOM # 2 IS DESIGNED |
| AS THE SPECIFICATION B THEN THE REQUIREMENTS HAVE BEEN |
| SATISFIED. |
| |
| 2B) SHEET A3.22 DETAIL # 9 ONLY GIVE THE REQUIRED |
| LOCATION FOR THE BACKING AND GRAB BAR FOR THE TOE END |
| OF THE TUB. NOT THE BACK WALL NOR THE HEAD OF THE TUB. |
| SEE FIGURE "4" FROM FAIR HOUSING REQS. IN 2010 FAC & |
| ALSO 24 CFR 100.205. |
| |
| 3) SHT. A-3.10 & A-.21 - WATER SUPPLY VALVES FOR THE |
| STACKED WASHER/DRYER UNIT SHALL BE ACCESSIBLE PER 2010 |
| FPC SEC.606.3. |
| |
| 4) SHT. A-3.41 - SHOW THE LENGTH AND WIDTH DIMENSIONS |
| OF THE ACCESSIBLE TOILET ROOMS ON DETAILS #3 & #4. |
| |
| 5)WHEN SUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION |
| |