Plan Review Notes
Plan Review Notes For Permit 16080618
Permit Number 16080618
Review Stop M
Sequence Number 1
Notes
Date Text
2016-08-24 08:19:171ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16080618
 8/24/16
  
 1) SUBMIT AC LOAD CALCULATIONS FOR THE NEW AC SYSTEMS-
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION,
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF THE NEW AC CONDENSERS.
  
 4) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE
 CONDENSERS AND STANDS TO THE ROOF STRUCTURE- SECTION
 301.15. SUBMIT NOA # 13-1017.09 WITH REVIEW SIGNATURE
 BY THE EOR.
  
 5) PROVIDE INSTALLATION DETAILS FOR THE NEW AHU'S AND
 MMU.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  