Plan Review Notes For Permit 16080613 |
Permit Number |
16080613 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-15 09:19:20 | THE PREVIOUS COMMENTS ARE TO BE ADVISORY ONLY. | | | | THE PLAN ADEQUATELY DISPLAYS COMPLIANCE WITH 1-3. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | 2016-09-12 13:54:50 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | 1] ADD SERVICE OUTLET BY THE CU, THE RECEPTACLE MUST BE | | GFCI AND LISTED "WR/WP". FBC-R SECTION E3901.11 | | | | 2] THE CONTROLLED LIGHTING OUTLET IN THE ATTIC ENTRANCE | | MUST BE NEAR AHU EQUIPMENT REQUIRING SERVICE. FBC-R | | SECTION E3903.4 | | | | 3] AFCI PROTECTION REQUIRED PER FBC-R SECTION E | | 3902.12. ADD TO GENERAL ELECT NOTES. | | | | 4] PERMANENT LIGHTING SHALL BE 75 % HIGH EFFICIENCY AND | | RECCESSED FIXTURES WILL BE LISTED IC-RATED SEALED TO | | NOT COMPROMISE THE BUILDING THERMAL ENVELOPE. FBC-E | | SECTIONS R402.4.4 & R404.1 ADD TO GENERAL ELECT NOTES. | | | | |
|