Plan Review Notes
Plan Review Notes For Permit 16080576
Permit Number 16080576
Review Stop P
Sequence Number 1
Notes
Date Text
2016-09-01 10:25:371ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. LABE THEL P-TRAP LOCATED DOWN STEAM OF MASTER
 BATHROOM ON RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
 2. KITCHEN SINK IS NOT VENTED IT SHALL COMPLY WITH FBC
 PL P3101.2.1 VENTING REQUIRED.
 EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
 3. A CLEANOUT IS REQUIRED WHERE THE 4IN BRANCH FOR KIT
 , LAUNDRY EXITS BUILDING BEFORE IT CONNECTS TO
 SEWER.PER FBC PL P3005.2.7
  
 4. A TRAP PRIMER IS REQUIRED ON ALL FLOOR DRAINS. PER
 FBC PL P3201.2 TRAP SEALS AND TRAP SEAL PROTECTION.
 TRAPS SHALL HAVE A LIQUID SEAL NOT LESS THAN 2 INCHES
 (51 MM) AND NOT MORE THAN 4 INCHES (102 MM). TRAPS FOR
 FLOOR DRAINS SHALL BE FITTED WITH A TRAP PRIMER OR
 SHALL BE OF THE DEEP SEAL DESIGN. TRAP SEAL PRIMER
 VALVES SHALL CONNECT TO THE TRAP AT A POINT ABOVE THE
 LEVEL OF THE TRAP SEAL.