Plan Review Notes For Permit 16080576 |
Permit Number |
16080576 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-31 18:15:19 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. | | | | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | (1) PROVIDE ON PLANS SIZE OF DUCT FEEDING DISTRIBUTION | | BOX FOR DUCTS FEEDING THE LAUNDRY AND CABANA BATH. | | (2) PROVIDE FLEX DUCT SIZE FOR 2" X 48" SIDEWALL | | FEEDING FOYER & SITTING ROOM. | | (3) PROVIDE FLEX DUCT SIZE FOR 2" X 48" SIDEWALL | | FEEDING THE LIVING ROOM | | (4) PROVIDE ALL EXHAUST FANS IN BATHROOMS CFM & EXHAUST | | DUCT SIZES. | | (5) SHOW TERMINATION OF DRYER EXHAUST. | | (6) SHOW LOCATION OF CONDENSING UNIT. | | (7) PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014. | | (8) IS THERE A KITCHEN EXHAUST??? IF THERE IS PROVIDE | | KITCHEN EXHAUST DUCT SIZING, TERMINATION AND TOTAL CFM. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (9) FORM R405-2014 MUST BE SIGNED BY OWNER/AGENT. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|