2016-08-17 10:25:25 | JOB PERMIT NUMBER: 16080576 |
| JOB ADDRESS: 925 39TH COURT |
| WEST PALM BEACH FLORIDA |
| DATE: AUGUST 17, 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1) SMOKE ALARMS REQUIRED IN EACH SLEEPING ROOM, OUTSIDE |
| OF EACH SLEEPING AREA, AND ON ANY ADDITIONAL HABITABLE |
| STORY OF A DWELLING. REFLECT LOCATION ON PLANS, THEY |
| SHALL BE INTERCONNECTED AND PROTECTED BY AN ARC-FAULT |
| BKR UNLESS EXCEPTIONS APPLY. FBC-R314 |
| 2) CARBON MONOXIDE ALARMS REQUIRED WITHIN 10' OF EACH |
| SLEEPING ROOM WHERE A FOSSIL FUEL APPLIANCE, FIREPLACE, |
| OR AN ATTACHED GARAGE IS PRESENT. REFLECT LOCATION ON |
| PLANS, THEY SHALL BE INTERCONNECTED AND PROTECTED BY AN |
| ARC-FAULT BKR UNLESS EXCEPTIONS APPLY. FBC-R315 |
| 3) SHEET E-1.0, IF ON THE MASTER BATH 2 SEPARATE OR A |
| DOUBLE SINK IS GONA BE USED ADD A 20 AMP GFCI OUTLET |
| WITHIN 3' OF THE BASIN EDGE AS PER FBC-R SECTION |
| E3901.6 |
| 4) SHEET E-1.0, INSTALL A 20 AMP GFCI OUTLET WITHIN |
| 12'' OF THE TOP OF THE COUNTER-TOP ON THE KITCHEN |
| ISLAND. FBC-R SECTION E3901.4.2 |
| 5) SHEET E-1.0, GARAGE DOOR OPENER OUTLET NOT SHOWN, |
| KEEP IN MIND THE RECEPTACLE SHALL BE GFCI PROTECTED PER |
| FBC-R SECTION E3902.2 |
| 6) SHEET E-1.0, ADD A GFCI OUTLET IN THE FRONT AND BACK |
| OF THE HOUSE, PLUS THE OUTSIDE LOGGIA REQUIRES 1 |
| RECEPTACLE ACCESSIBLE WITHIN 6.5' FROM GRADE. FBC-R |
| SECTION E3901.7 |
| 7) SHEET E-1.0, LAUNDRY ROOM DOESN'T SHOW LOCATION OF |
| WASHER AND DRYER OUTLETS. KEEP IN MIND ANY ADDITIONAL |
| RECEPTACLE WITHIN THE LAUNDRY ROOM SHALL BE GFCI |
| PROTECTED. FBC-107 MINIMUM PLAN REVIEW |
| 8) PROVIDE LOCATION OF THE NEW 200 AMP PANEL ''A'' ON |
| THE FLOOR PLAN TO VERIFY WORKING CLEARANCE AND A PANEL |
| SCHEDULE WITH MATCHING CIRCUITS. FBC-107 MINIMUM PLAN |
| REVIEW. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. WHEN RESUBMITTING, FOR A |
| QUICKER RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED |
| TO PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING |
| EACH ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL |
| FORM. |
| THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S |
| COMMENTS AND YOUR RESPONSE OR ACTION TO SAME. |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| APPRECIATED. |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |