Plan Review Notes
Plan Review Notes For Permit 16080576
Permit Number 16080576
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-17 10:25:25JOB PERMIT NUMBER: 16080576
 JOB ADDRESS: 925 39TH COURT
 WEST PALM BEACH FLORIDA
 DATE: AUGUST 17, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1) SMOKE ALARMS REQUIRED IN EACH SLEEPING ROOM, OUTSIDE
 OF EACH SLEEPING AREA, AND ON ANY ADDITIONAL HABITABLE
 STORY OF A DWELLING. REFLECT LOCATION ON PLANS, THEY
 SHALL BE INTERCONNECTED AND PROTECTED BY AN ARC-FAULT
 BKR UNLESS EXCEPTIONS APPLY. FBC-R314
 2) CARBON MONOXIDE ALARMS REQUIRED WITHIN 10' OF EACH
 SLEEPING ROOM WHERE A FOSSIL FUEL APPLIANCE, FIREPLACE,
 OR AN ATTACHED GARAGE IS PRESENT. REFLECT LOCATION ON
 PLANS, THEY SHALL BE INTERCONNECTED AND PROTECTED BY AN
 ARC-FAULT BKR UNLESS EXCEPTIONS APPLY. FBC-R315
 3) SHEET E-1.0, IF ON THE MASTER BATH 2 SEPARATE OR A
 DOUBLE SINK IS GONA BE USED ADD A 20 AMP GFCI OUTLET
 WITHIN 3' OF THE BASIN EDGE AS PER FBC-R SECTION
 E3901.6
 4) SHEET E-1.0, INSTALL A 20 AMP GFCI OUTLET WITHIN
 12'' OF THE TOP OF THE COUNTER-TOP ON THE KITCHEN
 ISLAND. FBC-R SECTION E3901.4.2
 5) SHEET E-1.0, GARAGE DOOR OPENER OUTLET NOT SHOWN,
 KEEP IN MIND THE RECEPTACLE SHALL BE GFCI PROTECTED PER
 FBC-R SECTION E3902.2
 6) SHEET E-1.0, ADD A GFCI OUTLET IN THE FRONT AND BACK
 OF THE HOUSE, PLUS THE OUTSIDE LOGGIA REQUIRES 1
 RECEPTACLE ACCESSIBLE WITHIN 6.5' FROM GRADE. FBC-R
 SECTION E3901.7
 7) SHEET E-1.0, LAUNDRY ROOM DOESN'T SHOW LOCATION OF
 WASHER AND DRYER OUTLETS. KEEP IN MIND ANY ADDITIONAL
 RECEPTACLE WITHIN THE LAUNDRY ROOM SHALL BE GFCI
 PROTECTED. FBC-107 MINIMUM PLAN REVIEW
 8) PROVIDE LOCATION OF THE NEW 200 AMP PANEL ''A'' ON
 THE FLOOR PLAN TO VERIFY WORKING CLEARANCE AND A PANEL
 SCHEDULE WITH MATCHING CIRCUITS. FBC-107 MINIMUM PLAN
 REVIEW.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES. WHEN RESUBMITTING, FOR A
 QUICKER RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING
 EACH ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL
 FORM.
 THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S
 COMMENTS AND YOUR RESPONSE OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  