Plan Review Notes For Permit 16080576 |
Permit Number |
16080576 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-31 14:01:31 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS | | (INCLUDING OVERHEAD GARAGE DOOR). | | 2. PROVIDE DESIGN WIND LOADS FOR ALL NEW OPENINGS. | | 3. PROVIDE LANDINGS AT ALL EXT DOORS. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND | | DOOR SUBMITTALS. | | | | FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN | | PRESSURES PURSUANT TO FBC-R301.2. | | | | R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. | | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH | | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE | | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A | | MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE | | DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE | | PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT | | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). | | | | | | |
|