Plan Review Notes For Permit 16080550 |
Permit Number |
16080550 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-10-19 11:54:32 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO'S: | | | | 1] FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING | | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC | | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN | | CONDITIONED & UNCONDITIONED SPACES. | | | | 2] PER FBC-E SECTION C405.7 A MINIMUM OF 50% OF ALL | | 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY | | CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES, | | COMPUTER CLASSROOMS, AND MODULAR PARTITIONS. | | | | |
|