Plan Review Notes For Permit 16080550 |
Permit Number |
16080550 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-15 16:08:34 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | 1) NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL | | BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR | | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY | | BE ON OWN CIRCUIT. | | | | 2) FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING | | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC | | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN | | CONDITIONED & UNCONDITIONED SPACES. ADD A NOTE ! | | | | 3) PROVIDE THE EXISTING ELECTRIC SERVICE RISER WITH | | WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. | | COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW | | CIRCUITS ON FLOOR PLAN. | | | | 4) PER FBC-E SECTION C405.7 A MINIMUM OF 50% OF ALL | | 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY | | CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES, | | COMPUTER CLASSROOMS, AND MODULAR PARTITIONS. ADD A NOTE | | ! | | | | |
|