Plan Review Notes
Plan Review Notes For Permit 16080550
Permit Number 16080550
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-15 16:08:34REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 2) FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. ADD A NOTE !
  
 3) PROVIDE THE EXISTING ELECTRIC SERVICE RISER WITH
 WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL.
 COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW
 CIRCUITS ON FLOOR PLAN.
  
 4) PER FBC-E SECTION C405.7 A MINIMUM OF 50% OF ALL
 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES,
 COMPUTER CLASSROOMS, AND MODULAR PARTITIONS. ADD A NOTE
 !
  
  