Plan Review Notes
Plan Review Notes For Permit 16080548
Permit Number 16080548
Review Stop P
Sequence Number 1
Notes
Date Text
2016-09-10 06:52:591) SHT. 077-A2.0 - DETAIL #5 - THE CAFE COUNTER SHALL
 BE A MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR. FL.
 ACCESS CODE ACC. SEC. 212, 606.
 2)SHT. 077 - A2.0 - DETAIL #4 - THE 3 COMPARTMENT SINK
 SHOWN IN THE MEN'S RESTROOM SHALL COMPLY WITH FAC
 SEC.212.3, 213.3.4.
 3) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE OUTLET
 OF THE OIL SEPARATOR FOR THE UTILITIES DEPT. TO SAMPLE
 THE EFFLUENT.
 4) SHT.203 - P2.1 - FLAT DRY VENTS ARE SHOWN ON THE OIL
 SEPARATOR. THE VENTS SHALL CONNECT ABOVE THE CENTERLINE
 OF THE DRAIN PIPE PER THE FPC SEC.905.3.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW