2016-08-18 14:09:23 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | 1) PROVIDE GFCI PROTECTION FOR THE KITCHEN COUNTER-TOP | | RECEPTACLES. NEC 210.8.A.6 [ADD TO OUTLET SYMBOL] | | | | 2) TAMPER-RESISTANT RECEPTACLES REQUIRED PER NEC 406.12 | | [ADD A NOTE] | | | | 3) SMOKE ALARMS REQUIRED PER FBC-R 314 & 315. IF | | EXISTING MAKE A NOTE |
|