Plan Review Notes For Permit 16080449 |
Permit Number |
16080449 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-08-23 18:26:33 | RESIDENTIAL (R3) STORM PANELS, SECOND BUILDING REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- SHUTTERS INSTALLATION SCHEDULE WAS REVISED. NOW IT | | SHOWS CONCRETE AND WOOD SUBSTRATE. SAME ANCHOR CAN NOT | | BE USED FOR THE DIFFERENT SUBSTRATES. SEE NEW PRODUCT | | APPROVAL FL11969-R3 SUBMITTED AND REVISE AS REQUIRED. | | CLEARLY IDENTIFY THE SHUTTER MOUNTING CONNECTION | | SECTION SHOWN ON THE PRODUCT APPROVAL FOR EACH | | SUBSTRATE TO VERIFY SPECIFIED ANCHORS. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | 2- BASED ON THE EDGE DISTANCE SHOWN, THE ANCHOR SPACING | | NEEDS TO BE REVISED. SEE SHEET 10 OF 15. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)[email protected] |
|