2016-08-15 11:29:11 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER ? PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| DATE: 8/15/16 |
| |
| 1. VALUE APPEARS LOW. |
| 2. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED. |
| 3. PROVIDE ENERGY CALCULATIONS. |
| 4. PROVIDE SOILS REPORT. |
| 5. PROVIDE WINDOW AND DOOR SCHEDULE. |
| 6. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND EXT. |
| DOORS. |
| 7. PROVIDE DESIGN WIND LOADS FOR OPENINGS. |
| 8. PROVIDE ROOF FRAMINJG PLAN. |
| 9. PROVIDE 2ND FLOOR PLAN. |
| 10. PROVIDE FOUNDATION PLAN WITH FOOTING AND BEAM |
| SCHEDULES. |
| 11. PROVIDE SITE PLAN WITH SETBACKS OF NEW |
| CONSTRUCTION. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY |
| DELAY THE APPLICATION PROCESS. |
| |
| BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES |
| MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE |
| SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM |
| BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH |
| THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT |
| MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE |
| THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL |
| PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
| |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| R401.4 SOIL TESTS. |
| WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL |
| SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, |
| SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE |
| LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL |
| DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE |
| THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. |
| THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN |
| APPROVED METHOD. |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY |
| FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| WINDOW AND DOOR SUBMITTALS. |
| |
| FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-R301.2. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |