Plan Review Notes
Plan Review Notes For Permit 16080378
Permit Number 16080378
Review Stop G
Sequence Number 2
Notes
Date Text
2016-08-27 04:30:151) THE GAS RISER SHOWS 3/4 INCH METALLIC PIPE AT THE
 METER . REFER TO 2014 FGC TABLE 402.4 (2) FOR CORRECT
 SIZING OF THE GAS SYSTEM.AS DRAWN, IT IS UNDERSIZED.
 2) SHOW THE LOCATION OF ANY DOORS OR WINDOWS ON THE
 FLOOR PLAN AND THE DISTANCE FROM THESE OPENINGS TO THE
 TANKLESS WATER HEATER. COMPLY WITH THE 2014 FGC SEC.
 503.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  