2016-08-09 17:12:16 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: 1383 10TH ST. |
| JOB ADDRESS: 1383 10TH ST. |
| DESCRIPTION: SERVICE CHANGE |
| MASTER PERMIT: 16080355 |
| |
| 1. NEC 408.3: PANEL RATING OF 125 AMP IS NOT SUFFICIENT |
| TO COMPLY WITH CODE REQUIREMENTS. |
| 2. RISER DIAGRAM & PANEL DESCRIPTION AS SUBMITTED DO |
| NOT MATCH. CORRECT ACCORDINGLY. |
| 3. NEC 230.6: YOU SHALL PROVIDE A SITE/FLOOR PLAN SHOW |
| THE LOCATION OF THE PANELS AND THE METER AND MAIN |
| DISCONNECT IF ANY. |
| 4. NEC 230.70: YOU ARE REQUIRED TO PROVIDE A DISCONNECT |
| FOR THE SERVICE CONDUCTORS BEFORE THEY ENTER THE |
| PREMISES; THE PANEL AS DESCRIBED IS A MLO. CORRECT |
| ACCORDINGLY. |
| 5. FBC-107.1: THE CITY OF WEST PALM BEACH AMENDMENTS TO |
| THE FBC SECTION 107.2.1 REQUIRE THAT ALL SUBMITTED |
| DRAWINGS FOR PERMIT APPROVAL BEAR THE NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. THE |
| PLANS FOR THE ABOVE MENTIONED JOB DO NOT HAVE THE NAME |
| OR SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| 6. FBC-R314: YOU SHALL COME INTO COMPLIANCE WITH THE |
| SMOKE DETECTOR REQUIRMENTS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |