Plan Review Notes
Plan Review Notes For Permit 16080314
Permit Number 16080314
Review Stop E
Sequence Number 2
Notes
Date Text
2016-09-29 12:41:14REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] PLANS MUST BE SUBMITTED AS A PACKAGE WITH ALL
 ARCHITECTURAL, MECHANICAL, PLUMBING, ALONG WITH
 ELECTRICAL SHEETS IN ORDER TO COMPLETE A QUALITY
 REVIEW. FBC 107
  
 2] NEW ELECTRICAL PLANS DON'T MATCH THE DESIGN OF
 RECORD INCORRECT SHEET #, WALL CONFIGURATION CHANGES,
 AND ETC.
  
 3] MISSING A SMOKE ALARM IN THE VICINITY OUTSIDE OF
 EACH SLEEPING AREA ( BEDROOMS ). FBC-R 314.3