Plan Review Notes For Permit 16080314 |
Permit Number |
16080314 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-09-29 12:41:14 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | 1] PLANS MUST BE SUBMITTED AS A PACKAGE WITH ALL | | ARCHITECTURAL, MECHANICAL, PLUMBING, ALONG WITH | | ELECTRICAL SHEETS IN ORDER TO COMPLETE A QUALITY | | REVIEW. FBC 107 | | | | 2] NEW ELECTRICAL PLANS DON'T MATCH THE DESIGN OF | | RECORD INCORRECT SHEET #, WALL CONFIGURATION CHANGES, | | AND ETC. | | | | 3] MISSING A SMOKE ALARM IN THE VICINITY OUTSIDE OF | | EACH SLEEPING AREA ( BEDROOMS ). FBC-R 314.3 |
|