Plan Review Notes
Plan Review Notes For Permit 16080314
Permit Number 16080314
Review Stop G
Sequence Number 1
Notes
Date Text
2016-08-29 11:34:301) A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED ON THE
 GAS BECAUSE THE TYPE OF PIPE BEING INSTALLED WAS NOT
 INDICATED ON THE GAS PLAN.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
 3.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 5) ) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3, FBCR SEC. G 2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  