Plan Review Notes For Permit 16080314 |
Permit Number |
16080314 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-29 11:34:30 | 1) A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED ON THE | | GAS BECAUSE THE TYPE OF PIPE BEING INSTALLED WAS NOT | | INDICATED ON THE GAS PLAN. | | 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 | | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G | | 2407. | | 3.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE | | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS | | SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. | | 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | 5) ) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE | | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS | | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE | | THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC | | SEC.402.3, FBCR SEC. G 2413.3. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|