| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1) THE SMALL ELECTRICAL SHEETS SHALL BE A MINIMUM 1/8'' |
| SCALE FOR THE QUALITY OF THE REVIEW. FBC 107 |
| 2) AT LEAST ONE WALL SWITCHED CONTROLLED LIGHTING |
| OUTLET SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH |
| GRADE LEVEL ACCESS. FBC-R SECTION E3903.3 |
| 3) SMOKE ALARMS REQUIRED PER FBC-R 314 & CARBON |
| MONOXIDE ALARMS REQUIRED PER FBC-R315 [ DUE TO |
| FIRE-PLACE ]. VERIFY ALL LOCATIONS REQUIRED BY CODE. |
| 4) ALL NEWLY INSTALLED RECEPTACLES SHALL BE |
| TAMPER-RESISTANT. FBC-R SECTION E4002.14 [ A NOTE WILL |
| SUFFICE ] |
| 5) ALL NEWLY MODIFIED CIRCUITS SHALL COMPLY WITH AFCI |
| PROTECTION IN AREAS REQUIRED. FBC-R SECTION E3902.13 [ |
| A NOTE WILL SUFFICE ] |
| 6) INSTALL AN OUTLET IN THE FRONT AND BACK OF THE |
| HOUSE. THE OUTDOOR RECEPTACLE SHALL BE GFCI PROTECTED. |
| FBC-R SECTION E3901.7 |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES.WHEN RESUBMITTING, FOR A QUICKER |
| RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED TO |
| PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING EACH |
| ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL FORM. |
| THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S |
| COMMENTS AND YOUR RESPONSE OR ACTION TO SAME. |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| APPRECIATED. |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |