Plan Review Notes
Plan Review Notes For Permit 16080300
Permit Number 16080300
Review Stop M
Sequence Number 2
Notes
Date Text
2016-10-28 08:56:552ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080300
 10/28/16
  
 1) THE LETTER FROM ROCAMAR ENGINEERING HAS BEEN
 FORWARDED TO ROBERT BROWN- BUILDING OFFICIAL FOR
 REVIEW. FINAL APPROVAL OF THE MECHANICAL PLANS ARE
 CONTINGENT ON APPROVAL OF THE LETTER REQUEST TO EXCLUDE
 EXHAUST VENTILATION FOR THE ART CLASSROOMS, AND TO
 RETAIN THE CURRENT MECHANICAL DESIGN.
  
 2) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE PER
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. NOTE 20
 ON SHEET A100 IS INDICATING WOOD.
  
 3) PLEASE PROVIDE ON THE PLAN THE FABRIC DUCT
 MANUFACTURER AND SUBMIT SPECIFICATIONS WITH APPROVAL
 SIGNATURE BY THE EOR- SECTION 603.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  