Plan Review Notes
Plan Review Notes For Permit 16080300
Permit Number 16080300
Review Stop Z
Sequence Number 1
Notes
Date Text
2016-08-11 16:29:318/11/16- FAILED
  
 ZONE- NC NEIGHBORHOOD COMMERCIAL
  
 FAILED
 1. PLEASE PROVIDE DRAWINGS FOR CURB CUT IT MUST BE
 20FT. OR LESS AND A 3FT. SIDE SETBACK.
  
 PASSED
 1. 5 REQUIRED PARKING SPACES 5 PARKING SPACES PROVIDED.
 2. 1 HANDICAPPED SPACE PROVIDED ONE HANDICAPPED SPACE
 PROVIDED.
 3. 9FT. WIDE REGULAR SPACE MEETS THE 8FT. WIDE SPACE
 REQUIRED.
 4. 18FT. LONG REGULAR PARKING SPACE PROVIDED 16FT. LONG
 REQUIRED.
 5. HANDICAPPED SPACE MEETS THE 12FT. WIDE 16FT. LONG
 SPACE REQUIREMENT.
 6. GROUND COVERAGE IS 32.53% MEETING THE 60%
 REQUIREMENT.
 7. 18.14% LANDSCAPING MEETING THE 15% LANDSCAPING
 REQUIREMENT.
 8. ONE(1)STORY BUILDING MEETING THE ONE 30FT. HEIGHT
 LIMIT.
 9. MORE THAN 10FT. BUILDING SEPORATION.
 10. BIKE RACK BEING ADDED.
 11. DIRECTIONAL SIGNS INCLUDED.