Plan Review Notes
Plan Review Notes For Permit 16080300
Permit Number 16080300
Review Stop M
Sequence Number 1
Notes
Date Text
2016-09-07 12:42:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080300
 9/7/16
  
 1) REFER TO TABLE 403.3: ART CLASSROOMS ARE REQUIRED TO
 HAVE EXHAUST AT A RATE OF 0.7 CFMS PER SQ. FT. AND
 RECIRCULATION OF AIR FROM THE SPACES IS PROHIBITED PER
 FOOTNOTE G, EXCEPT THAT RECIRCULATION SHALL BE
 PERMITTED WHERE THE RESULTING SUPPLY AIRSTREAM CONSISTS
 OF NOT MORE THAN 10 PERCENT AIR RECIRCULATED FROM THESE
 SPACES (SEE SECTION 403.2.1, ITEMS 2 AND 4). PLEASE
 REVISE THE PLANS AND VENTILATION CALCULATIONS
 ACCORDINGLY, IDENTIFY THE SPACES USE FOR ART
 INSTRUCTION, AND SHOW THE REQUIRED EXHAUST SYSTEMS.
  
 2) THE SUBMITTED COMCHECK COMPLIANCE CERTIFICATE
 INDICATES RTU-1 FOR THE ART SECTION, HOWEVER THE PLANS
 ARE INDICTICATING TWO SPLIT AC SYSTEMS- PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  