Plan Review Notes For Permit 16080300 |
Permit Number |
16080300 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-07 12:42:45 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16080300 | | 9/7/16 | | | | 1) REFER TO TABLE 403.3: ART CLASSROOMS ARE REQUIRED TO | | HAVE EXHAUST AT A RATE OF 0.7 CFMS PER SQ. FT. AND | | RECIRCULATION OF AIR FROM THE SPACES IS PROHIBITED PER | | FOOTNOTE G, EXCEPT THAT RECIRCULATION SHALL BE | | PERMITTED WHERE THE RESULTING SUPPLY AIRSTREAM CONSISTS | | OF NOT MORE THAN 10 PERCENT AIR RECIRCULATED FROM THESE | | SPACES (SEE SECTION 403.2.1, ITEMS 2 AND 4). PLEASE | | REVISE THE PLANS AND VENTILATION CALCULATIONS | | ACCORDINGLY, IDENTIFY THE SPACES USE FOR ART | | INSTRUCTION, AND SHOW THE REQUIRED EXHAUST SYSTEMS. | | | | 2) THE SUBMITTED COMCHECK COMPLIANCE CERTIFICATE | | INDICATES RTU-1 FOR THE ART SECTION, HOWEVER THE PLANS | | ARE INDICTICATING TWO SPLIT AC SYSTEMS- PLEASE CLARIFY. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|