Plan Review Notes
Plan Review Notes For Permit 16080300
Permit Number 16080300
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-07 17:11:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080300
 ADD: 5016 SOUTH DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-762-2713
 E-MAIL: NO E-MAIL ADDRESS PROVIDED FOR
 COMMUNICATION!!!!!!!!!
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 07/2016
 ACTION: DENIED
  
 1) THE COVERSHEET UNDER THE HEADING PROJECT INFORMATION
 LIST THIS AS A BUSINESS OCCUPANCY, TRAINING AND SKILL
 DEVELOPMENT, NOT ASSOCIATED WITH A SCHOOL. DEPENDING ON
 THE AGE OF THE STUDENTS THIS OCCUPANCY COULD BE ANY OF
 THE THREE, DAY CARE I-4 , EDUCATIONAL OR BUSINESS ?
 2014 FBC-B ,308.6 305.1 & B 304.1.
 PLEASE PROVIDE THE AGE GROUP OF THE STUDENTS, IF THE
 BUILDING IS TO BE USED BY MULTIPLE AGE GROUPS, THEN IT
 WOULD BE CONSIDERED A MIXED USE OCCUPANCY. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) SHEET SP-1 SEPARATE PERMITS ARE REQUIRED FOR PAVING
 AND STRIPPING, LANDSCAPE, IRRIGATION, AWNINGS AND SIGNS
 ARE UNDER SEPARATE PERMIT, REVIEWS AND FEES. 105.1
 REQUIRED PERMITS.
  
 3) SHEET SP-1 SHOWS WORK ON THE LOT TO THE NORTH BEING
 ACCOMPLISHED UNDER THIS PERMIT. PLEASE NOTE THE LOT TO
 THE NORTH 5008 S. DIXIE IS ALSO OWNER BY A DIFFERENT
 OWNER AND WOULD REQUIRE A SEPARATE PERMIT.
 105.1 REQUIRED PERMITS.
  
 4) BOTH SHEETS SP-1 AND S-1 SHOW A NEW ACCESSIBLE
 PARKING SPACE, PLEASE SEE THE CITY OF WEST PALM BEACH
 MUNI CODE SECTION 94-485 FOR THE REQUIRED COLOR AND
 STRIPING OF AN ACCESSIBLE PARKING SPACE AND ACCESS
 AISLE.
 ACCESS. CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE
 MARKED SO AS TO DISCOURAGE PARKING IN THEM.
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED.
  
 5) SHEET S-1 WILL NEED TO SHOW THE ELEVATION OF THE 2
 CORNER OF THE ACCESSIBLE PARKING SPACE AND THE OPPOSITE
 CORNERS OF THE ACCESS AISLE FOR COMPLIANCE WITH:
 ACCESS. CODE 502.4 FLOOR OR GROUND SURFACES. PARKING
 SPACES AND ACCESS AISLES SERVING THEM SHALL COMPLY WITH
 302. ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE
 PARKING SPACES THEY SERVE. CHANGES IN LEVEL ARE NOT
 PERMITTED. EXCEPTION: SLOPES NOT STEEPER THAN 1:48
 SHALL BE PERMITTED.
  
 6) SHEET S-1 THE BOTTOM PORTION OF THE RAMP. THE BOTTOM
 LANDING HAS A ELEVATION MARK OF 15.10 FT., THE
 MID-LANDING A ELEVATION MARK OF 15.53 FT. MIDWAY UP THE
 RAMP THERE IS AN ELEVATION MARKED 15.03? IS THIS A
 TYPO? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 7) SHEET S-2 SHOWS THE NEW ACCESSIBLE RAMP A SECTION
 4/S-3. THIS IS SECTION THROUGH THE RAMP IN A NORTH
 SOUTH DIRECTION. WHEN VIEWING THIS DETAIL THERE SHOWS A
 HANDRAIL SYSTEM, ALSO SEE SHEET A2 DETAIL 6. THERE IS A
 NOTE THAT THE ADA APPROVED HANDRAIL IS TO BE APPROVED
 BY THE OWNER.
 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS
 FOR HANDRAILS FOR RAMPS:
 2014 ACCESS. CODE 505.3 ? 505.10.2. ALL SECTIONS.
  
 8) SHEET A1 INDICATES A NEW DOOR OPENING AND THE
 EXISTING WINDOWS BEING REPLACED, SHEET S3 PROVIDES
 STRUCTURAL DETAILS FOR THE NEW DOOR OPENING AND A
 INFILL OF A DOOR TO NEW WINDOW OPENING. THE PLANS DO
 NOT PROVIDE THE WIND DESIGN CRITERIA;
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 8.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 8.2. RISK CATEGORY.
  
 8.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 8.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 8.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 9) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 10) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) SHEET A100 THE ACCESSIBLE RESTROOM 107 HAS 2 WATER
 CLOSETS IN THE ONE RESTROOM. THE SMALLER CHILDS WATER
 CLOSET DOES NOT MEET THE SIDE CLEARANCE REQUIREMENTS OF
 ACCESS. CODE 604.3.1 BOTH THE OTHER WATER CLOSET AND
 DIAPER CHANGING TABLE ARE IN THE WAY.
  
 12) PLEASE NOTE CHILDRENS WATER CLOSETS ARE AGE
 SPECIFIC TO THE AGE OF THE CHILDREN SEE 604.9 AND
 ADVISORY 604.9. FOR CENTERLINES, TOILET SEAT HEIGHT,
 GRAB BAR HEIGHT AND DISPENSER HEIGHTS.
  
 13) ACCESSIBILITY DETAIL SHEET A000:
 13A) THE WATER CLOSET GRAB RAILS ARE SHOWN AS BEING
 MEASURED FROM THE CENTERLINE OF THE GRAB BAR. PLEASE
 UPDATE PLANS THE 2014 FBC-ACCESS. CODE 609.4 MEASURES
 THE GRAB BAR FROM THE TOP OF THE GRASPING SURFACE NOT
 THE CENTERLINE.
  
 13B) THE TYPICAL HANDICAPPED SIGNAGE IS SHOWN CENTERED
 AT THE HEIGHT OF 5 FOOT.
 2014 ACCESS. CODE 703.4.1 HEIGHT ABOVE FINISH FLOOR OR
 GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48
 INCHES (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 LOWEST TACTILE CHARACTER AND 60 INCHES (1525 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE HIGHEST TACTILE
 CHARACTER.
  
 14) FURTHER COMMENTS MAY BE FORTH COMING DEPENDING ON
 THE MECHANICAL REVIEW COMMENTS ADDITIONAL FRESHAIR WILL
 BE REQUIED AND POSSIBLY ADDTIONAL A/C EQUIPMENT ON THE
 ROOF TOP, 2014 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
  
 15) THIS PLAN MAY END UP A CHANGE IN OCCUPANCY IF SO
 THEN IMPACT FEE ASSESSMENT SHALL OCCUR. BEFORE A PERMIT
 TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID
 TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2016-08-19 15:18:36PRODUCT APPROVAL TO BE DEFERRED PER EMAIL FROM STEVEN