2016-09-07 17:11:56 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16080300 |
| ADD: 5016 SOUTH DIXIE HWY. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-762-2713 |
| E-MAIL: NO E-MAIL ADDRESS PROVIDED FOR |
| COMMUNICATION!!!!!!!!! |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. SEPT. 07/2016 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET UNDER THE HEADING PROJECT INFORMATION |
| LIST THIS AS A BUSINESS OCCUPANCY, TRAINING AND SKILL |
| DEVELOPMENT, NOT ASSOCIATED WITH A SCHOOL. DEPENDING ON |
| THE AGE OF THE STUDENTS THIS OCCUPANCY COULD BE ANY OF |
| THE THREE, DAY CARE I-4 , EDUCATIONAL OR BUSINESS ? |
| 2014 FBC-B ,308.6 305.1 & B 304.1. |
| PLEASE PROVIDE THE AGE GROUP OF THE STUDENTS, IF THE |
| BUILDING IS TO BE USED BY MULTIPLE AGE GROUPS, THEN IT |
| WOULD BE CONSIDERED A MIXED USE OCCUPANCY. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 2) SHEET SP-1 SEPARATE PERMITS ARE REQUIRED FOR PAVING |
| AND STRIPPING, LANDSCAPE, IRRIGATION, AWNINGS AND SIGNS |
| ARE UNDER SEPARATE PERMIT, REVIEWS AND FEES. 105.1 |
| REQUIRED PERMITS. |
| |
| 3) SHEET SP-1 SHOWS WORK ON THE LOT TO THE NORTH BEING |
| ACCOMPLISHED UNDER THIS PERMIT. PLEASE NOTE THE LOT TO |
| THE NORTH 5008 S. DIXIE IS ALSO OWNER BY A DIFFERENT |
| OWNER AND WOULD REQUIRE A SEPARATE PERMIT. |
| 105.1 REQUIRED PERMITS. |
| |
| 4) BOTH SHEETS SP-1 AND S-1 SHOW A NEW ACCESSIBLE |
| PARKING SPACE, PLEASE SEE THE CITY OF WEST PALM BEACH |
| MUNI CODE SECTION 94-485 FOR THE REQUIRED COLOR AND |
| STRIPING OF AN ACCESSIBLE PARKING SPACE AND ACCESS |
| AISLE. |
| ACCESS. CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE |
| MARKED SO AS TO DISCOURAGE PARKING IN THEM. |
| THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO |
| DESIGNATE IT AS A NO-PARKING ZONE. |
| ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE |
| TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT |
| THE AISLE BE CLEARLY MARKED. |
| |
| 5) SHEET S-1 WILL NEED TO SHOW THE ELEVATION OF THE 2 |
| CORNER OF THE ACCESSIBLE PARKING SPACE AND THE OPPOSITE |
| CORNERS OF THE ACCESS AISLE FOR COMPLIANCE WITH: |
| ACCESS. CODE 502.4 FLOOR OR GROUND SURFACES. PARKING |
| SPACES AND ACCESS AISLES SERVING THEM SHALL COMPLY WITH |
| 302. ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE |
| PARKING SPACES THEY SERVE. CHANGES IN LEVEL ARE NOT |
| PERMITTED. EXCEPTION: SLOPES NOT STEEPER THAN 1:48 |
| SHALL BE PERMITTED. |
| |
| 6) SHEET S-1 THE BOTTOM PORTION OF THE RAMP. THE BOTTOM |
| LANDING HAS A ELEVATION MARK OF 15.10 FT., THE |
| MID-LANDING A ELEVATION MARK OF 15.53 FT. MIDWAY UP THE |
| RAMP THERE IS AN ELEVATION MARKED 15.03? IS THIS A |
| TYPO? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| 7) SHEET S-2 SHOWS THE NEW ACCESSIBLE RAMP A SECTION |
| 4/S-3. THIS IS SECTION THROUGH THE RAMP IN A NORTH |
| SOUTH DIRECTION. WHEN VIEWING THIS DETAIL THERE SHOWS A |
| HANDRAIL SYSTEM, ALSO SEE SHEET A2 DETAIL 6. THERE IS A |
| NOTE THAT THE ADA APPROVED HANDRAIL IS TO BE APPROVED |
| BY THE OWNER. |
| PLEASE SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS |
| FOR HANDRAILS FOR RAMPS: |
| 2014 ACCESS. CODE 505.3 ? 505.10.2. ALL SECTIONS. |
| |
| 8) SHEET A1 INDICATES A NEW DOOR OPENING AND THE |
| EXISTING WINDOWS BEING REPLACED, SHEET S3 PROVIDES |
| STRUCTURAL DETAILS FOR THE NEW DOOR OPENING AND A |
| INFILL OF A DOOR TO NEW WINDOW OPENING. THE PLANS DO |
| NOT PROVIDE THE WIND DESIGN CRITERIA; |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 8.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 8.2. RISK CATEGORY. |
| |
| 8.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 8.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 8.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 9) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 10) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 11) SHEET A100 THE ACCESSIBLE RESTROOM 107 HAS 2 WATER |
| CLOSETS IN THE ONE RESTROOM. THE SMALLER CHILDS WATER |
| CLOSET DOES NOT MEET THE SIDE CLEARANCE REQUIREMENTS OF |
| ACCESS. CODE 604.3.1 BOTH THE OTHER WATER CLOSET AND |
| DIAPER CHANGING TABLE ARE IN THE WAY. |
| |
| 12) PLEASE NOTE CHILDRENS WATER CLOSETS ARE AGE |
| SPECIFIC TO THE AGE OF THE CHILDREN SEE 604.9 AND |
| ADVISORY 604.9. FOR CENTERLINES, TOILET SEAT HEIGHT, |
| GRAB BAR HEIGHT AND DISPENSER HEIGHTS. |
| |
| 13) ACCESSIBILITY DETAIL SHEET A000: |
| 13A) THE WATER CLOSET GRAB RAILS ARE SHOWN AS BEING |
| MEASURED FROM THE CENTERLINE OF THE GRAB BAR. PLEASE |
| UPDATE PLANS THE 2014 FBC-ACCESS. CODE 609.4 MEASURES |
| THE GRAB BAR FROM THE TOP OF THE GRASPING SURFACE NOT |
| THE CENTERLINE. |
| |
| 13B) THE TYPICAL HANDICAPPED SIGNAGE IS SHOWN CENTERED |
| AT THE HEIGHT OF 5 FOOT. |
| 2014 ACCESS. CODE 703.4.1 HEIGHT ABOVE FINISH FLOOR OR |
| GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 |
| INCHES (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR |
| GROUND SURFACE, MEASURED FROM THE BASELINE OF THE |
| LOWEST TACTILE CHARACTER AND 60 INCHES (1525 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE, |
| MEASURED FROM THE BASELINE OF THE HIGHEST TACTILE |
| CHARACTER. |
| |
| 14) FURTHER COMMENTS MAY BE FORTH COMING DEPENDING ON |
| THE MECHANICAL REVIEW COMMENTS ADDITIONAL FRESHAIR WILL |
| BE REQUIED AND POSSIBLY ADDTIONAL A/C EQUIPMENT ON THE |
| ROOF TOP, 2014 FBC-M- 301.15 WIND RESISTANCE. |
| MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH |
| THE FLORIDA BUILDING CODE, BUILDING. |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS |
| |
| 15) THIS PLAN MAY END UP A CHANGE IN OCCUPANCY IF SO |
| THEN IMPACT FEE ASSESSMENT SHALL OCCUR. BEFORE A PERMIT |
| TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID |
| TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS |
| MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |
| 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
2016-08-19 15:18:36 | PRODUCT APPROVAL TO BE DEFERRED PER EMAIL FROM STEVEN |
| VITEK SR. PROJECT MANAGER STEVEN E. MYOTT, ARCHITECT |
| |
| |
| |