Plan Review Notes For Permit 16080298 |
Permit Number |
16080298 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-08-16 07:52:34 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16080298 | | 8/16/16 | | | | 1) REFER TO SECTION 501.2 FBC-14 MECHANICAL. THE DRYER | | EXHAUST AND THE KITCHEN HOOD EXHAUST CAN NOT BE IN THE | | SAME CHASE AS THE BATHROOM EXHAUST- PLEASE CORRECT. | | | | 2) INDICATE THE DIMENSIONS OF THE MAIN SUPPLY PLENUM | | AND VERIFY IT IS SIZED LARGE ENOUGH FOR 1600 CFMS. | | PLEASE NOTE THAT A 35X5" DUCT IS UNDERSIZED PER ASHRAE | | APPROVED DUCTULATORS. | | | | 3) NOTE #2 IS INDICATING THE NEW CEILING HEIGHT WILL BE | | 7 FT. PLEASE SEE SECTION 1208.2 FBC-14 BUILDING AND | | VERIFY THAT THE 7 FT. CEILING HEIGHT IS LIMITED TO THE | | KITCHEN, THE BATHROOMS, THE LAUNDRY ROOM, AND STORAGE | | ROOMS. | | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER. | | PLEAS NOTE MAKEUP AIR MAY BE REQUIRED PER SECTION | | 504.5. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|