Plan Review Notes
Plan Review Notes For Permit 16080298
Permit Number 16080298
Review Stop M
Sequence Number 1
Notes
Date Text
2016-08-09 09:16:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080298
 8/9/16
  
 1) PLEASE ENLARGE THE PRINT SO THAT ALL RIGID AND FLEX
 DUCT SIZES, DIFFUSER SIZES, AND SUPPLY CFMS CAN BE SEEN
 CLEARLY FOR REVIEW.
  
 2) THE RETURN AIR SYSTEM APPEARS TO BE AN ABOVE-CEILING
 RETURN AIR PLENUM. PLEASE PLACE A NOTE ON THE PLAN TO
 CLEARLY IDENTIFY IT AS SUCH, AND REFER TO SECTION
 606.2.2.1 FOR MATERIALS WITHIN PLENUMS.
  
 3) INDICATE HOW AIR IS BEING RETURNED FROM THE LIVING
 ROOM AND BREAKFAST ROOM. DOES THE HALL CLOSET HAVE A
 LOUVERED DOOR AND A RETURN GRILL IN THE CEILING? PLEASE
 SEE SECTION C403.2.7.2 FOR MECHANICAL CLOSET
 COMPLIANCE.
  
 4) CLARIFY THE PURPOSE OF THE HOOD EXHAUST IN THE
 LAUNDRY ROOM, INDICATE THE MAKE AND MODEL OF THE
 APPLIANCE IT IS SERVING. PLEASE NOTE THAT IF WHAT IS
 DEPICTED IS DRYER EXHAUST, THEN THE EXHAUST DUCT SHALL
 BE MINIMUM 4" IN DIAMETER PER SECTION 504.6.1.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 WASHER/DRYER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  