2016-08-09 09:16:55 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16080298 | | 8/9/16 | | | | 1) PLEASE ENLARGE THE PRINT SO THAT ALL RIGID AND FLEX | | DUCT SIZES, DIFFUSER SIZES, AND SUPPLY CFMS CAN BE SEEN | | CLEARLY FOR REVIEW. | | | | 2) THE RETURN AIR SYSTEM APPEARS TO BE AN ABOVE-CEILING | | RETURN AIR PLENUM. PLEASE PLACE A NOTE ON THE PLAN TO | | CLEARLY IDENTIFY IT AS SUCH, AND REFER TO SECTION | | 606.2.2.1 FOR MATERIALS WITHIN PLENUMS. | | | | 3) INDICATE HOW AIR IS BEING RETURNED FROM THE LIVING | | ROOM AND BREAKFAST ROOM. DOES THE HALL CLOSET HAVE A | | LOUVERED DOOR AND A RETURN GRILL IN THE CEILING? PLEASE | | SEE SECTION C403.2.7.2 FOR MECHANICAL CLOSET | | COMPLIANCE. | | | | 4) CLARIFY THE PURPOSE OF THE HOOD EXHAUST IN THE | | LAUNDRY ROOM, INDICATE THE MAKE AND MODEL OF THE | | APPLIANCE IT IS SERVING. PLEASE NOTE THAT IF WHAT IS | | DEPICTED IS DRYER EXHAUST, THEN THE EXHAUST DUCT SHALL | | BE MINIMUM 4" IN DIAMETER PER SECTION 504.6.1. | | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | WASHER/DRYER. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|