2016-09-13 18:47:04 | 9/13/16 RESPONDED TO CHRIS' EMAIL ADDRESSING MY PLAN |
| REVIEW NOTES. SEE EMAIL IN SENT FOLDER DATED 9/13/16 TO |
| CHRIS. |
2016-08-17 15:31:29 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: UB KINSEY EDUCATIONAL & COMMUNITY CENTER |
| JOB ADDRESS: 720 8TH STREET |
| DESCRIPTION: LOW VOLTAGE FIRE ALARM INSTLLATION |
| MASTER PERMIT: 10010548 |
| SUB PERMIT: 16080296 |
| |
| THE SYSTEM AS DESIGNED DOES NOT COMPLY WITH THE |
| OCCUPANCY CLASSIFICATION OF THE PROTECTED PREMISES. |
| YOUR PLANS INCORRECTLY DETERMINED THAT THE OCCUPANCY IS |
| BUSINESS, WHEN IN-FACT IT IS EDUCATIONAL. SEE FBC-B |
| SECTION 453, FBC-B 907.2.3, AND THE APPROVED MASTER |
| PERMIT LIFE SAFETY PLANS. CHECK THE SYSTEM DESIGN AND |
| CORRECT ACCORDINGLY. NEVER THE LESS, BELOW PLEASE FIND |
| A LIST OF REQUIRED CORRECTIONS REQUIRED WITH THE PLANS |
| AS SUBMITTED. ADDITIONAL CORRECTIONS MAY BE REQUIRED |
| AFTER REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PER SECTION FBC-B 453.7.6 THE F/A SHALL SHUT OFF GAS |
| AND FUEL OIL SUPPLIES WHICH SERVE STUDENT OCCUPIED |
| SPACES OR PASS THROUGH SUCH SPACES. THIS MAY BE |
| APPLICABLE TO LAB CLASSROOMS IF ANY. |
| 2. PER SECTION FBC-B 453.7.6.1 KITCHEN FUEL GAS SHALL |
| BE SHUT OFF BY ACTIVATION OF HOOD SYSTEM. |
| 3. THE PLANS SHALL BE MARKED WITH THE ACTUAL CODE TO |
| WHICH THE SYSTEM IS BEING DESIGNED. |
| 4. THE FCPS SPEC SHEET PROVIDED IS FOR THE 6 AMP MODEL, |
| YET YOUR BATTERY CALCULATIONS CHART ADDRESSES BOTH THE |
| 6 & THE 8 AMP MODEL. INDICATE WHICH MODEL WILL BE USED. |
| 5. YOU PROVIDED SPEC SHEETS FOR ALL BUT THE BATTERIES; |
| EACH APPARATUS REQUIRES A DIFFERENT BATTERY. IDENTIFY |
| WHAT BATTERY WILL BE IN EACH. |
| 6. CORRECT THE MATH FOR THE WATT LOSS CALCULATIONS. |
| 7. ADD A BLOCK NOTE ADDRESSING THE NFPA 70 SECTION |
| 760.41(B) OR 760.121(B) & NFPA 72 SECTION 10.5.5.2 ? |
| 10.5.5.3. |
| 8. RELOCATE MANUAL PULL STATION IN THE LOBBY TO COMPLY |
| WITH NFPA SECTION 17.14.6. |
| 9. PER THE APPROVED LIFE SAFETY PLAN SHEET LS1, THERE |
| IS AN EXIT OUT OF STAIRWAY 2 THAT IS MISSING FROM THE |
| DRAWING. CORRECT ACCORDINGLY AND INCLUDE REQUIRED |
| DEVICE. |
| 10. IF GAZEBO IS LESS THAN 10? FROM THE BLDG. |
| STRUCTURE, AN INITIATION DEVICE SHALL BE REQUIRED. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |