2016-08-17 15:31:29ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: UB KINSEY EDUCATIONAL & COMMUNITY CENTER
 JOB ADDRESS: 720 8TH STREET
 DESCRIPTION: LOW VOLTAGE FIRE ALARM INSTLLATION
 MASTER PERMIT: 10010548
 SUB PERMIT: 16080296
  
 THE SYSTEM AS DESIGNED DOES NOT COMPLY WITH THE
 OCCUPANCY CLASSIFICATION OF THE PROTECTED PREMISES.
 YOUR PLANS INCORRECTLY DETERMINED THAT THE OCCUPANCY IS
 BUSINESS, WHEN IN-FACT IT IS EDUCATIONAL. SEE FBC-B
 SECTION 453, FBC-B 907.2.3, AND THE APPROVED MASTER
 PERMIT LIFE SAFETY PLANS. CHECK THE SYSTEM DESIGN AND
 CORRECT ACCORDINGLY. NEVER THE LESS, BELOW PLEASE FIND
 A LIST OF REQUIRED CORRECTIONS REQUIRED WITH THE PLANS
 AS SUBMITTED. ADDITIONAL CORRECTIONS MAY BE REQUIRED
 AFTER REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PER SECTION FBC-B 453.7.6 THE F/A SHALL SHUT OFF GAS
 AND FUEL OIL SUPPLIES WHICH SERVE STUDENT OCCUPIED
 SPACES OR PASS THROUGH SUCH SPACES. THIS MAY BE
 APPLICABLE TO LAB CLASSROOMS IF ANY.
 2. PER SECTION FBC-B 453.7.6.1 KITCHEN FUEL GAS SHALL
 BE SHUT OFF BY ACTIVATION OF HOOD SYSTEM.
 3. THE PLANS SHALL BE MARKED WITH THE ACTUAL CODE TO
 WHICH THE SYSTEM IS BEING DESIGNED.
 4. THE FCPS SPEC SHEET PROVIDED IS FOR THE 6 AMP MODEL,
 YET YOUR BATTERY CALCULATIONS CHART ADDRESSES BOTH THE
 6 & THE 8 AMP MODEL. INDICATE WHICH MODEL WILL BE USED.
 5. YOU PROVIDED SPEC SHEETS FOR ALL BUT THE BATTERIES;
 EACH APPARATUS REQUIRES A DIFFERENT BATTERY. IDENTIFY
 WHAT BATTERY WILL BE IN EACH.
 6. CORRECT THE MATH FOR THE WATT LOSS CALCULATIONS.
 7. ADD A BLOCK NOTE ADDRESSING THE NFPA 70 SECTION
 760.41(B) OR 760.121(B) & NFPA 72 SECTION 10.5.5.2 ?
 10.5.5.3.
 8. RELOCATE MANUAL PULL STATION IN THE LOBBY TO COMPLY
 WITH NFPA SECTION 17.14.6.
 9. PER THE APPROVED LIFE SAFETY PLAN SHEET LS1, THERE
 IS AN EXIT OUT OF STAIRWAY 2 THAT IS MISSING FROM THE
 DRAWING. CORRECT ACCORDINGLY AND INCLUDE REQUIRED
 DEVICE.
 10. IF GAZEBO IS LESS THAN 10? FROM THE BLDG.
 STRUCTURE, AN INITIATION DEVICE SHALL BE REQUIRED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  