Plan Review Notes For Permit 16080290 |
Permit Number |
16080290 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-11-09 16:50:31 | MECHANICAL PROVISOS: | | FBC-14 MECHANICAL | | 11/9/16 | | | | 1) THE OUTSIDE AIR INTAKE SHALL BE LOCATED A MINIMUM OF | | 10' HORIZONTALLY FROM THE REAR DRIVEWAY AND PARKING | | AREA- SECTION 401.4 | | | | 2) THE EXHAUST OUTLETS SHALL TERMINATE A MINIMUM OF 10' | | ABOVE ADJOINING GRADE- SECTION 501.3.1 |
|