2016-10-28 15:46:433RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080290
 10/28/16
  
 1) SHEET M1: THE AC SYSTEM IS NOTED AS EXISTING WITH NO
 CHANGES IN HOWEVER THERE IS AN EQUIPMENT SCHEDULE FOR A
 NEW 7.5 TON SPLIT SYSTEM ON THE PLAN, AND ALSO A NOTE
 SPECIFYING RELOCATION AND INSTALLATION OF DROPS AND
 RETURNS. PLEASE NOTE THE ELECTRICAL PQNEL SCHEDULE
 INDICATES AN RTU. PLEASE CLARIFY THE SCOPE OF THE
 PROPOSED PROJECT.
  
 2) M-1: PROVIDE A DETAIL FOR INSTALLATION OF THE NEW
 AIR HANDLER (IF APPLICABLE) AND HOW THE RETURN DUCT
 SPECIFED AS "SURFACE MOUNTED" WILL CONNECT TO THE UNIT.
 INDICATE THE HEIGHT FROM THE FINISHED FLOOR TO THE
 UNDERSIDE OF THE SURFACE MOUNTED RETURN.
  
 3) M-1: SHOW THE COMPONENTS OF THE SOURCE CAPTURE
 SYSTEM AT THE NAIL STATIONS INCLUDING THE EXHAUST DUCT
 RUNS FROM THE POINT OF CAPTURE TO THE DISCHARGE
 LOCATIONS AND THE TYPES AND SIZES OF DUCTWORK. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE MANICURE TABLES
 AND ALL ASSOCIATED PRODUCTS WITH APPROVAL SIGNATURES BY
 THE DESIGNER OF RECORD.
  
 4) M-1: INDICATE THE TYPE AND SIZE OF OUTSIDE AIR VENT
 TO BE INSTALLED AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND A FL. PRODUCT APPROVAL AND/OR
 MIAMI-DADE NOA- SECTION 401.5. INDICATE WITH A NOTE, OR
 SHOW MEASUREMENTS TO VERIFY THE LOCATION OF THE AIR
 INLET MEETS THE MNINIMUM REQUIRED CLEARANCE DISTANCES
 PER SECTION 401.4.
  
 5) SHOW THE LOCATION OF THE NEW AC CONDENSER AND
 PROVIDE ENGNEERING FOR INSTALLATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER