2016-10-13 11:11:49 | 1ST REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| PREVIOUS COMMENTS |
| 1. NOT COMPLIED SHT. A-3 DETAIL #6 SHOULD REFLECT THE |
| PLAN.THE SIDE DIMENSION OF 60IN SHALL NOT HAVE ANY |
| OTHER FIXTURES IN THAT SPACE THE DETAIL IS SHOWING THE |
| LAVATORY. PER FBC ACC |
| 604.3.1 AND 604.3.2 OVERLAP. |
| THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| |
| 2. NOT COMPLIED. LAVATORY'S IN PUBLIC BATHROOMS SHALL |
| HAVE TEMPERED WATER DELIVERED FROM A TEMPERATURE |
| LIMITING DEVICE THE THERMOSTAT ON THE WATER HEATER DOES |
| NOT COMPLY. PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC |
| HAND-WASHING FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. AND 607.1.1 TEMPERATURE LIMITING |
| MEANS. |
| A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE |
| AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF |
| COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR |
| MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY |
| TEMPERATURE AT FIXTURES. |
| |
| 8. NOT COMPLIED THE WATER HEATER SHALL BE PROVIDED WITH |
| A MEANS OF CONTROLLING THERMAL EXPANSION THE |
| TEMPERATURE AND PRESSURE RELIER VALVE DOES NOT COMPLY |
| WITH THIS CODE SECTION. PER FBC PL 607.3 THERMAL |
| EXPANSION CONTROL. |
| A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY |
| THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN |
| ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. AND 504.4 |
| RELIEF VALVE. |
| STORAGE WATER HEATERS OPERATING ABOVE ATMOSPHERIC |
| PRESSURE SHALL BE PROVIDED WITH AN APPROVED, |
| SELF-CLOSING (LEVERED) PRESSURE RELIEF VALVE AND |
| TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF. THE |
| RELIEF VALVE SHALL CONFORM TO ANSI Z21.22. THE RELIEF |
| VALVE SHALL NOT BE USED AS A MEANS OF CONTROLLING |
| THERMAL EXPANSION. |
| |
| 11. NOT COMPLIED. SHOW THE SHUT OFF ON THE COLD WATER |
| MAIN AND ALL THE DROPS. PER FBC PL |
| 606.1 LOCATION OF FULL-OPEN VALVES. |
| FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| |
| 2. ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE |
| ENTRANCE INTO THE STRUCTURE. |
| |
| |
| 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN |
| OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL |
| OCCUPANCIES. |
| |